Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
RS485 / RS232 / Ethernet
Document code: MN67038_ENG Revision 2.003 Page 28 of 42
The means of the fields for “RS232/RS485/RS422” are:
The field “
Enable Serial
” is used for selecting if the serial is used (field checked) or not (field unchecked). For the codes with only
one serial, this field isn’t editable (it is always checked); for the codes with two serials, at least one of the two must be checked.
In the field “
Port
” the port used to communicate with converter using TCP/UDP protocol is defined. The port of second serial must be
different from the first one;
In the field “
Socket Disconnect TimeOut (Seconds)
” a time in seconds is defined. If no data pass through the socket for the
seconds defined, the socket disconnects.
In the field “
Baudrate
” the data rate of the serial line in use is defined;
In the field “
Parity
” the parity of the serial line in use is defined;
In the field “
Data Bits
” the number of data bits used for the serial line communication is defined;
In the field “
Stop Bit
” the number of Stop bits used for the serial line communication is defined;
In the field “
Data Packing
” the serial to Ethernet conversion’s method is defined:
o
Default: standard way defined in the firmware;
o
Length: defined number of bytes in the field on the right;
o
Timeout: after a defined time with no communication in the field on the right;
o
Delimiter: after a specific char defined in the field on the right.
If the field “
TCP
” is checked, the Protocol used is the TCP, if the field “
UDP
” is checked, the Protocol used is the UDP. Only if the
protocol is “TCP”, it is possible to select the field “
Force socket TCP open
”. When it is selected, the converter opens the TCP
connection with the end-point automatically at start-up and, if the end-point closes the connection, the converter tries to reopen it
cyclically.