![Adeunis RF SIGFOX SENSORS User Manual Download Page 32](http://html1.mh-extra.com/html/adeunis-rf/sigfox-sensors/sigfox-sensors_user-manual_2850725032.webp)
SIGFOX SENSORS - Mode d’emploi / User guide version V2.1.1
32
Page
of 45
GB
1.4. Technical Specifications
1.4.1 General characteristics
Parameters
Value
Power supply voltage
3.6 V nominal
Power supply
Integrated Li-SOCl2 battery (radio management and querying of meters)
Operating temperature
-25°C / +70°C
Dimensions
105 x 50 x 27mm
Case
IP 67
SIGFOX Certification
SIGFOX Certification number : P_001F_3A67_02
Radio standards
EN 300-220, EN 301-489
1.4.2 Product input tolerance characteristics
Parameters
Value
Max input voltage
10V
Dry contact detection level
0.5V
Analog input accuracy
12 bits
Input resistance (dry contact version)
100 Ohm
1.4.3 Battery life
Conditions of use
Transmission frequency
Number of meters
battery life
Product storage before use: 1 year
maximum.
Calculations carried out at a tempera-
ture of 20°C
140 frames per day
1 ou 2
0.5 year
100 frames per day
1 ou 2
0.7 year
50 frames per day
1 ou 2
1.3 year
20 frames per day
1 ou 2
3 years
2 frames per day
1 ou 2
+10 years
1.4.4 Operating modes
SIGFOX SENSORS has two states (modes) of operation.
• STANDBY
: this is the mode in which you receive your product (no transmission of radio frames).
• OPERATION
: this is the mode in which SIGFOX SENSORS transmits frames periodically. To switch to this mode of operation, you need to
activate the product with a magnet (see §2.6 Product start-up).
1.4.5 Sensors compatibility
Examples of sensors tested by Adeunis (non-exhaustive list)
Type
Name
Type
Applications
4-20mA
EE80
E+E Electronik
CO2, temperature, relative humidity
Buildings technical management, air quality,
ventilation, etc...
4-20mA
PR791F
Asco Instrument
Pressure
Industrial processes, static and dynamic
measurements, etc...
0-10V
PF211
Mitchell instruments
Relative humidity
Heating, ventilation and air conditioning and
regulating ambient conditions...
0-10V
ADT 23-110
MSR Electronic
Nitrogen dioxide NO2
NO2 detection in underground garages,
tunnels, shelters, industrial zones, etc...
Dry Contact
RBWF-LF
S+S Regeltechnik
Luminosity, movements and motions
Building technical management, motion
detection for management of lighting, venti-
lation, etc...
Summary of Contents for SIGFOX SENSORS
Page 4: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 4 Page of 45 FR FRANCAIS...
Page 6: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 6 Page of 45 FR...
Page 25: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 25 Page of 45 GB ENGLISH...
Page 27: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 27 Page of 45 GB...