Low threshold value channel A
Decimal
Default : 0
For a 4-20mA sensor:
• Unit: x 10nA
• Min/Max values: 400 000 to 2 000 000
E.g.: if S326=600 000, the low threshold will have a value of
600000x10=6 000 000nA i.e. 6mA
For a 0-10V sensor:
• Unit: x 1µV
• Min/Max values: 0 à 10 000 000
E.g.: if S326=1 000 000, the high threshold will have a value of
1 000 000µV i.e. 1V
S327
3
Value of the low threshold
hysteresis of channel A:
Decimal
Default : 0
For a 4-20mA sensor:
• Units : x 10nA
• Min/Max values: 0 to 1 600 000
E.g.: if S327=200 000, the value of the low threshold hysteresis
will be 200000x10=2 000 000nA i.e.2mA
For a 0-10V sensor:
• Unit: x 1µV
• Min/Max values: 0 à 10 000 000
E.g.: if S327=3 000 000, the value of the low threshold hystere-
sis will be 3 000 000µV i.e. 3V
S328
3
High threshold value channel B
Decimal
See details of register 324
S329
3
Value of the high threshold
hysteresis of channel B:
Decimal
See details of register 325
S330
3
Low threshold value channel B
Decimal
See details of register 326
S331
3
Value of the low threshold
hysteresis of channel B:
Decimal
See details of register 327
3.4.2
Network registers
The list of registers below allows you to change the behavior of the product application. This list is accessible in
Provider mode following execution of the ATT63 Provider command.
These registers must be handled with caution because they could cause problems of communication or of
non-compliance with the legislation in force.
Regis-
ter
Size
(bytes)
Description
Coding
Details
S202
4
Number of repetitions in
the case of a uplink frame
associated with a downlink
frame
Decimal
Default: 2
Min/max: 0 to 2
Unit: none
IMPORTANT:
This number of repetitions only concerns the
uplink frames after which the product will open a
listening window for a downlink frame.
S317
1
Enabling the respect of the
Duty Cycle
Decimal
Default : 1 (enabled)
Min/max : 0 (disabled) or 1 (enabled)
Unit: none
WARNING :
Deactivation of the Duty Cycle may result in a
violation of the conditions of use of the frequency
band, depending on the use of the product, thus
violating the regulations in force.
In the case of disabling the Duty Cycle, the re-
sponsibility is transferred to the user.