sigfox RC1 ANALOG - Guide utilisateur / User guide version V2.0.1
56
Page
of 86
FR
2.1.4
REPLI mode
The product enters this very low consumption mode following the detection of a level of battery that is too low. In
this mode the product wakes up every 5 seconds to make the red LED flash twice.
The replacement of the battery (if the product is a replaceable battery version) followed by the application of the
magnet takes the product out of this mode to return it to the operating mode.
2.2. Application operation
2.2.1
Periodic transmission
The product allows the measurement and the periodic transmission of the values of the sensors according to the
following diagram:
The settings associated with this mode of operation are:
• the transmission period (register 301).
• the presence and type of external sensor (registers 320 and 322).
A complete list of the registers can be found in paragraph 3.4.
Eg:
Registre
Value encoding
Value
Result
S301
Decimal
6
Periodic mode with a
period of 6x10min = 60
minutes
S320
Hexadecimal
0x02
Channel A configured for a
sensor 4-20mA
S322
Hexadecimal
0x01
Channel B configured for a
sensor 0-10V
Product in standby
Measurement input A
(if enabled)
Measurement input B
(if enabled)
Send frame 0x40
Period
reached?
YES
No