EN
sigfox RC1 ANALOG - Guide utilisateur / User guide version V2.0.1
59
Page
of 86
FR
FR
S325
Decimal
100 000
The value of the hysteresis of the high thresh-
old of channel A is: 100 000x10=1 000 000nA
so 1mA
S326
Decimal
600 000
The value of the low threshold of channel A is:
600 000x10=6 000 000nA so 6mA
S327
Decimal
100 000
The value of the hysteresis of the low threshold
of channel A is: 100 000x10=1 000 000nA so
1mA
S328
Decimal
8 000 000 The value of the high threshold of channel B is:
8 000 000µV so 8V
S329
Decimal
1 000 000 The value of the hysteresis of the high thresh-
old of channel B is: 1 000 000µV so 1V
S330
Decimal
3 000 000 The value of the low threshold of channel B is:
3 000 000µV so 3V
S331
Decimal
1 000 000 The value of the hysteresis of the low threshold
of channel A is: 1 000 000µV so 1V
2.2.3
Transmission on event of digital input
The product allows the measurement and the transmission of the values of the sensors following an event on a
digital input according to the following diagram:
This triggering can be on the rising edge, falling edge or both. A configurable debounce is present on every digital
input.
Input TOR1 is associated with channel A and input TOR2 with channel B.
The settings associated with this mode of operation are:
• The transmission periodicity (zero in this usage situation) (register 301)
• The presence and type of external sensor (registers 320 and 322).
•
The configuration of the events (registers 321 and 323).
A complete list of the registers can be found in paragraph 3.4.
Product in standby
Measurement input A
(if enabled)
Measurement input B
(if enabled)
Send frame 0x42
Change
on digital
input?
Oui
Non