Explanation of thresholds and hysteresis:
The monitoring period by the sensors is fixed at 10 minutes (to change this value, contact the Technical Support
Department).
The settings associated with this mode of operation are:
• The transmission periodicity (zero in this usage situation) (register 301).
• The presence and type of external sensor (registers 320 and 322).
•
The configuration of the events (registers 321 and 323).
• The high alarm threshold channel A (register 324).
• The high alarm hysteresis channel A (register 325).
• The low alarm threshold channel A (register 326).
• The low alarm hysteresis channel A (register 327).
• The high alarm threshold channel B (register 328).
• The high alarm hysteresis channel B (register 329).
• The low alarm threshold channel B (register 330).
• The low alarm hysteresis channel B (register 331).
A complete list of the registers can be found in paragraph 3.4.
E.g.:
Register
Value encoding
Value
Result
S301
Decimal
0
Event mode
S320
Hexadecimal
0x02
Channel A configured for a sensor 4-20mA
S322
Hexadecimal
0x01
Channel B configured for a sensor 0-10V
S321
Hexadecimal
0x03
On channel A:
Detection of high and low thresholds
Detection of event on disabled digital input
No waiting period
S323
Hexadecimal
0x02
On channel B:
Detection of high thresholds
Detection of event on disabled digital input
No waiting period
S324
Decimal
1 200 000 The value of the high threshold of channel A is:
1 200 000x10=12 000 000nA so 12mA
high threshold
Low threshold
High threshold -
high threshold hysteresis
Low thr
low threshold hysteresis
Sensor value
High alarm enabling
High alarm disabling
Low alarm enabling
Low alarm disabling