2.2.2 Periodic transmission with history
The product allows the accumulation of several successive meter values before the periodic transmission of the set of values according to the
following scheme:
Product in standby
Send frame 0x48
Historical
period rea-
ched
?
Yes
No
Detected
and valida-
ted pulse
?
Counting
of the impulse
Yes
No
No
Number of
recorded
values rea-
ched ?
Yes
The parameters associated with this mode of operation are:
•
Enabling and Configuring inputs (register 320)
•
History configuration (register S321)
•
Debounce timer period (registers S322)
A complete list of the registers can be found in paragraph 3.4.
Eg:
Registre
Value encoding
Value
Result
S320
Hexadecimal
0x39
Channel A :
• Activated
•
Meter other than gas
•
Tamper input activated
Channel B :
• Activated
•
Gas meter
•
Tamper input disabled
S321
Hexadecimal
0x02
Channels A and B : historical mode with backup of the
counters every hour and transmission every 24h so 24
values per counter
S322
Hexadecimal
0x57
Debounce :
•
Channel A = 500ms
•
Channel B = 100ms