AMR SENSORS- Mode d’emploi / User guide version V1.2
32
Page
of 41
3.4. Configuring the AMR SENSORS unit
Your AMR Sensors product is delivered with the following factory settings: WMBUST1 radio mode, sending interval of 10 minutes, and active
On-Off sensors 1 & 2. The combination of switches enables your AMR Sensors unit to be configured. The following parameters may be modified:
•
Transmission interval
•
Inputs activation (sensors 1 and 2)
•
The type of sensor connected (analogue or digital -On-Off-)
Note 1
: The Wireless M-Bus radio mode can only be configured using the WMBUS USB configuration key and the dedicated software. The
default radio mode is T1 mode.
Note 2
: Activation of the sensors and the type of sensors (analogue or digital -On-Off-) can only be done via the switches.
Seal
CONFIGURATION
TABLE:
Parameter
Value
SW1
SW2
SW3
(Sensor 1)
SW4
(Sensor 2)
SW5
(Sensor 1)
SW6
(Sensor 2)
Periodicity of radio transmission
10 seconds
ON
OFF
10 minutes
OFF
OFF
1 hour
OFF
ON
12 hours
ON
ON
Activation of sensors inputs
Sensors 1&2 inactifs
OFF
OFF
Sensor 1 actif
ON
OFF
Sensor 2 actif
OFF
ON
Sensor 1&2 actifs
ON
ON
Type of sensor
Sensor 1&2 ANA
OFF
OFF
Sensor 1&2 I/O
ON
ON
Sensor 1 ANA, Sensor 2 I/O
OFF
ON
Sensor 1 TOR, Sensor 2 I/O
ON
OFF
NB: E
ach change in a switch’s position is considered by the AMR Sensors unit to be a changeover to Configuration mode. The product therefore
then automatically returns to Standby position.
If you modify the product’s configuration, it will then be mandatory to switch (back) to Operations mode by passing a magnet near the activa-
tion system (cf. Chapter 3.6).
3.5. Closing the casing
Once stages 3.2, 3.3 and 3.4 have been carried out, you can close the casing of the AMR Sensors unit.
Procedure:
•
Make sure that the seal is properly positioned on the base