background image

VISTA-48D 

Security System 

 

 

 

 

Installation and Set-Up Guide

 

 
 
 
 
 
 

 

 

 
 
 

 
 
 
 
 

 

 

 

 

 

 

 
 
 
 
 
 

 

K0749-4EN 1/03         

Summary of Contents for VISTA-48D

Page 1: ...VISTA 48D Security System Installation and Set Up Guide K0749 4EN 1 03...

Page 2: ...ii...

Page 3: ...Module 2 9 Installing the Transmitters 2 9 Installing a Keyswitch 2 10 Connecting Relay Modules 2 11 Powerline Carrier Devices 2 12 On Board Triggers 2 13 Phone Line Connections 2 14 Alternative Commu...

Page 4: ...ng 82 Menu Mode 5 15 Configurable Zone Type Programming 83 Menu Mode 5 16 Programming Installer and User Schedules 5 18 System Communication and Operation 6 1 Panel Communication with Central Station...

Page 5: ...allow disarm the system Up to 4 Keypad macros which can be activated by wired wireless keypads Paging feature allows certain system conditions to be reported to up to 3 pager phone numbers can use a...

Page 6: ...ECP connection to Ethernet TCP IP Internet AC Power Supply Wired in or Plug in 110 e g 1321 220VAC transformer Important Installation Highlights Installer Please Read This system uses addressable key...

Page 7: ...with the latch bracket when the door is closed When correctly positioned push the lock until it is held securely by its snap tabs Notes The cabinet can be closed and secured without a lock by using 2...

Page 8: ...dditional screws 2 Insert grounding lugs supplied with the receiver through the top of the cabinet into the left hand terminals of the antenna blocks at the upper edge of the receiver board and secure...

Page 9: ...for each wire size Use supplementary power if the control s aux power load for all devices exceeds 600mA Suggested power supply AD12612 Keypad Addresses Keypad Address Keypad Address no 1 16 no 5 20 n...

Page 10: ...perform steps 2 and 3 if using a self activated siren Wiring the AC Transformer Transformer Connect the Transformer to terminals 1 and 2 on the control board See wiring table at right for wire size to...

Page 11: ...ly expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in areas of severe electrical activity te...

Page 12: ...Hardwire Type prompt option 3 basic wired zones are automatically paired as follows ZonePaired with zone 2 10 3 11 4 12 5 13 6 14 7 15 8 16 NOTE A short across the EOL i e at terminal on either zone...

Page 13: ...10 41 48 11 3 Connect sensors to the module s loops 4 If using relays with the 4229 connect the desired field wiring to the unit s relay contact terminals Notes Supports up to 40 expansion zones NO o...

Page 14: ...connect the desired field wiring to the keypad s relay contact terminals See 6164 Keypad Instructions for other mounting wiring and programming information Notes Each 6164 keypad supports up to 4 wire...

Page 15: ...m the microprocessors in those units Figure 9 5881EN RF Receiver cover removed Installing a 5800TM Module 1 Mount the 5800TM next to the RF receiver between one and two feet from the receiver s antenn...

Page 16: ...dard keypad cable as shown Connect the yellow and white keyswitch wires to trigger connector pin 3 12V Connect the Red and Green LED wires to the appropriate output 17 output 18 trigger connector pins...

Page 17: ...er is installed Alpha CHECK xx Wire Expansion FAULT xx Wire Expansion TAMPER xx Wire Expansion ALARM xx Wire Expansion Fixed Glass lxx or 91 if field 199 set for 2 digit display where xx is the module...

Page 18: ...data field 27 and enter the unit code using 79 Output Device menu Mode Notes When using Powerline Carrier devices you must use a Powerline Carrier Device Modulator It supplies signals from the control...

Page 19: ...devices These outputs are normally high and go low upon programmed condition The outputs can be programmed for inverted operation normally low go high using 79 Menu mode Program these triggers using...

Page 20: ...nals and voltage input terminals of the ACM to the control s keypad connection points Set the ACM s address to 03 following the instructions provided with the ACM Notes Use compatible ACMs e g 7845i 7...

Page 21: ...ine carrier zones chime zones night stay exit route zones final exit door zone and pager zones 82 Alpha Programming Create alpha descriptors for easy zone identification Scheduling Mode code 64 Create...

Page 22: ...RF House ID Code if using DIP switch equipped wireless keypads for each partition 25 Arming Prevention Override 67 Transmitter Low Battery Report Code 75 Transmitter Low Battery Restore Report Code 17...

Page 23: ...Zone types are defined below Zone Type Description Type 00 Zone Not Used Program a zone with this zone type if the zone is not used Type 01 Entry Exit Burglary 1 Assign to zones that are used for prim...

Page 24: ...Stay mode Type 12 Monitor Zone Works as a dynamic monitor of a zone fault trouble not alarm In the case of a short open the message ALARM 24 Hr Non Burg XXX where XXX is the zone number will be sent...

Page 25: ...re sent Type 82 Blockschloss Used with special blockschloss lock and key System arms 5 seconds after the key is fully turned arms MAXIMUM key can then be removed When armed the blockschloss zone is sh...

Page 26: ...umber and pager character fields Interactive Mode Programming 56 57 58 79 80 81 82 83 Entering Interactive Mode Press Interactive Mode No for example 56 while in Program Mode The Alpha display keypad...

Page 27: ...le 3 6164 relay only module 4 6164 relay only 12 13 14 15 112 113 114 115 79 output device programming device address prompt entered at device address prompt entered at device address prompt entered a...

Page 28: ...Installation Instructions 3 8...

Page 29: ...2 compliance 23 Quick Forced Bypass 0 no quick bypass 1 allow quick bypass code 6 All zones bypassed by this function will be displayed after the bypass is initiated 24 RF House ID Code 00 disable all...

Page 30: ...s Timing FIELD TITLE and DATA ENTRIES EXPLANATION 31 Single Alarm Sounding Per Zone per armed period 0 no limit on alarm sounding per zone 1 limit alarm sounding to once per arming period for a given...

Page 31: ...nused spaces 0 9 11 for 12 for 13 for a pause 2 seconds To clear entries from field press 40 If fewer than 6 digits need to be entered exit by pressing which advances to the next field Call Waiting If...

Page 32: ...digits 0 9 11 for B 12 for C 13 for D 14 for E 15 for F Enter up to 10 digits depending on the report format selected in field 48 52 Part 3 Secondary Subs Acct No Enter digits 0 9 11 for B 12 for C 1...

Page 33: ...stem is not disarmed before entry delay expires an EXIT ALARM message will be sent to the central station if Exit Error Report Code is enabled The keypad will display EA fixed word or EXIT ALARM alpha...

Page 34: ...Dec Enter the start and end month for summer time if applicable to the region 78 Summer Time Start End Weekend 0 disabled 4 fourth 1 first 5 last 2 second 6 next to last 3 third 7 third to last Enter...

Page 35: ...st zone as defined in zone list 8 is restored then there is 5 second exit delay before arming state is active Select the desired option NOTE Must be 0 if system uses zone type 82 blockschloss 89 Event...

Page 36: ...2 2 report pairs per zone per armed period This option can be used to limit the number of alarm alarm restore messages per zone sent to the central station in an armed period 94 Download Phone Number...

Page 37: ...ll users enabled to page 12 Alarms and troubles for zones entered in zone list 9 13 Alarms and troubles for zones listed in zone list 9 and opens closes for all users enabled to page Enter the types o...

Page 38: ...on 1 2 0 15 secs 6 2 1 2 min 12 8 min 1 30 secs 7 3 min 13 10 min 2 45 secs 8 4 min 14 12 min 3 60 secs 9 5 min 15 15 min 4 90 secs 10 6 min 5 2 min 11 7 min These entries set the duration for output...

Page 39: ...s when not in exit delay or 30 seconds after disarm 0 disable 1 enable Select the desired keypad display options Entry 1 If enabled only the first zone that went into alarm is displayed Pressing the R...

Page 40: ...ee field 190 for explanation 196 Keypad 8 Device Address 23 See field 190 for entries Keypad 8 See field 190 for explanation 197 Exit Time Display Interval 0 no display 1 5 seconds between display ref...

Page 41: ...to Confirm 0 no 1 yes If 1 Yes is entered the XMIT TO CONFIRM prompt appears later in this procedure after entering RF transmitter serial and loop numbers and lets you confirm the programming of each...

Page 42: ...s only for basic wired zones 01 08 zone 02 is used as an example in display NOTE If zone doubling is being used the response time set for zones 01 08 automatically applies to each zone s associated do...

Page 43: ...ered in error simply re enter the loop number or press and the serial number will return to the display XMIT TO CONFIRM PRESS TO SKIP Confirmation Option Activate the loop input or button to continue...

Page 44: ...Zn ZT P RC IN L 10 Summary Screen 01 64 zone number 00 quit to continue OR D to go to prompts for wireless key programming templates A summary screen will appear showing zone 1 s currently programmed...

Page 45: ...nly appear if the first prompt after entering 58 was answered Yes To confirm activate the loop input or button that corresponds to this zone The system checks for a duplicate If a duplicate exists a l...

Page 46: ...Start Zone Number to continue 8 The system will search for the highest available consecutive 4 zone group the four zones in the case of the 5804 and 5804BD and display the lowest zone number of the gr...

Page 47: ...the device and affix it in the appropriate column on the ENROLLED TRANSMITTERS worksheet of the Programming Form then enter the other information zone number zone type loop number etc relevant to tha...

Page 48: ...an entry Press to go forward again Output Device programming involves 1 Use 79 Menu Mode to assign module and output numbers and map them to device addresses NOTE You must map output devices using 79...

Page 49: ...keypad 2 Powerline Carrier device to continue Select whether this is a relay or a Powerline Carrier X 10 device If relay is selected skip to B prompt If X 10 is selected go to A prompt A XX UNIT No yy...

Page 50: ...vent Note that each defined function is associated with only one output number This means that if more than one output device needs to perform this particular function you need to define another outpu...

Page 51: ...e type was selected this screen appears Otherwise skip to the next row Enter the desired zone type associated with this output number See below for a list of available zone types CHOICES FOR ZONE TYPE...

Page 52: ...Action 0 6 see list at right Enter the desired device action as listed below Press the key to continue 0 off 4 Change Device State 1 Close for 2 seconds 5 Duration 1 see data field 177 2 Close and Sta...

Page 53: ...example 01 02 03 After all zones are entered press 00 to continue IMPORTANT Do not include fire zones in zone lists that are used to STOP device actions 01 Del Zn List 0 No 1 Yes 0 Deleting Zone Lists...

Page 54: ...Returns to key number prompt with the next function key letter displayed System defaults to these function key settings For Options 09 12 note that there are only four macros per system Therefore be...

Page 55: ...ds Pressing 0 goes to the next prompt to let you enter zone descriptors Pressing 1 lets you program a partition descriptor or reminder words If selected the following prompt appears PART REMIND Enter...

Page 56: ...a short 90 Resp to open Armed 0 DArmd 0 Response to Opens 0 none 2 trouble 1 Alarm 3 fault to continue Select the type of response when zones assigned to this zone type are opened when the system is a...

Page 57: ...D 000 Trouble ID 000 Contact ID Report Codes 000 999 report code to continue returns to Enter configurable zone type number prompt Enter the desired 3 digit Contact ID report codes for faults and trou...

Page 58: ...t number for event you want to occur at a specified time Events 10 11 are reserved for the installer only Child Not Home report option 03 is sent to all pagers in the user s partition message sent is...

Page 59: ...sing the key to move forward then press 1 to select the day s This entry applies only to the following events 1 relay on off 2 user access 3 child not home report use 00 23 if 24 hour time is enabled...

Page 60: ...Installation Instructions 5 20...

Page 61: ...LURE on alpha keypads or FC on fixed word keypads Report Code Formats The following chart indicates the types of handshake kissoff frequencies that the panel supports and the different formats that ca...

Page 62: ...e Res SSS S RT SSS S RT SSSS SS RTt RTRTRT RT t Bypass Res SSS S RB SSS S RB SSSS SS RBb RBRBRB RB b Characters in parenthesis are included in Robofon 8 format Where SSS or SSSS Subscriber ID C Close...

Page 63: ...de as in 4 2 format Signal flow Receiving equipment Dialing equipment Send start char w 77h Send message described above Acknowledge ACK 06h Delay greater than 500ms Send new start char w 77h Send nex...

Page 64: ...ision 341 Trouble ECP Cover Tamper 344 RF Receiver Jam Detect 351 Telecom Line Fault 353 Alternative Comm Media Trouble 354 Failure to Communicate log only 373 Fire Loop Trouble 374 Exit Error Alarm 3...

Page 65: ...tem only if it was used to arm the system 3 Duress see user performs security functions but also silently sends a duress message to the central station reports as duress code user number 4 Partition s...

Page 66: ...e key on the keypads see Single Button Arming above Arming Instant Enter code INSTANT 7 Arming Maximum Enter code MAXIMUM 4 or simply press appropriate lettered key on the keypads see Single Button Ar...

Page 67: ...ith the partition in which it is entered To include a 2 second dialing pause in the number press at the point in the entry the pause is desired it displays as Pauses entered at the end of the number w...

Page 68: ...th a zone number and a once per minute beeping at the keypad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless keypad If the battery is not re...

Page 69: ...l be transmitted with a TEST report The keypad will beep once per minute as a reminder that the system is in the Test mode NOTE Wireless motion detectors Passive Infrared units will send signals out o...

Page 70: ...u should reorient or move the transmitter to another location Usually a few centimeters in either direction is all that is required 4 If each transmitter produces the proper keypad response when it is...

Page 71: ...F multi frequency Data Tones 1400 2300Hz ACK 1400Hz KISSOFF Robofon Contact ID same as ADEMCO except 2300Hz ACK LINE SEIZE Double Pole DOC Load No 3 4 Maximum Zone Resistance Zones 1 8 300 ohms exclud...

Page 72: ...ic duct detector 2451 w DH400 base Ionization duct detector 1451D w DH400 base H Low profile Photoelectric w 57 C thermal 2100T Low profile Ionization type direct wire 1100 Transformers 1321 or 16 5VA...

Page 73: ...Hr Silent other zone responses are possible 5802CP Belt Clip Personal Emergency BR Only Same as 5802 5802MN 5802MN2 Miniature Personal Emergency Trans UR or RF Same as 5802 5804 Wireless Key Transmit...

Page 74: ...mpered cover switch Has 3 unique input loop codes Loop 1 Built in shock sensor loop wired to TB1 normally closed Loop 2 For a closed circuit contact loop using the built in reed switch in conjunction...

Page 75: ...8 5 NOTES...

Page 76: ...Installation Instructions 8 6 NOTES...

Page 77: ...on or intrusion that takes place behind walls cei lings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors win...

Page 78: ...1 House ID 2 8 4 1 9 3 9 4 IBM Personal Computer 3 1 Ideal Model 61 035 2 5 Input Device Type 5 4 9 3 9 4 Installer Code 3 6 4 1 8 1 8 2 Interior Follower 3 3 5 2 5 11 Interior w Delay 3 4 5 2 5 11 k...

Page 79: ...9 3 Figure 17 Summary of Connections...

Page 80: ...DENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT...

Reviews: