Mounting and Wiring the Control
2-7
Figure 7. 4-Wire Smoke Detector Connections
4-Wire Smoke Detector Using Relay for Power Reset
4-Wire Smoke Detector Using Output 17 for Power Reset
4219/4229 Expansion Zones
1. Connect each module to the control’s keypad terminals.
2. Assign each module a unique device address (07-11)
using its DIP switches. Device addresses determine
the zone numbers being used, as shown in the
following table.
Expander Module Addresses
For Zones… Set Module to Device Address…
09-16
07
(not available if zone-doubling enabled)
17-24
08
25-32
09
33-40
10
41-48
11
3. Connect sensors to the module’s loops.
4. If using relays with the 4229, connect the desired
field wiring to the unit's relay contact terminals.
Notes
Supports up to 40 expansion zones (NO or NC)
using 4219/4229 Zone Expander Modules as
follows:
Use 1000 ohm end-of-line resistors at the end of
loops connected to the 4219/4229 modules. (End-
of line resistors used on the control terminals are
2000 ohms.)
Expansion zones have normal response time
(400–500 msec), except zone connected to each
module’s loop “A,” which can be set for fast
response† (10–15 msec).
† Do not use fast response in Western Europe;
fast response is not permitted by
EN50131-1/prEN50131-3
.
Figure 8. Wiring Connections, 4219 & 4229 (4229 shown)
[RM2] Comentário:
moved address
table here from next column
Summary of Contents for VISTA-48D
Page 1: ...VISTA 48D Security System Installation and Set Up Guide K0749 4EN 1 03...
Page 2: ...ii...
Page 28: ...Installation Instructions 3 8...
Page 60: ...Installation Instructions 5 20...
Page 75: ...8 5 NOTES...
Page 76: ...Installation Instructions 8 6 NOTES...