ADEMCO 4110XM Installation Instructions Manual Download Page 4

–5–

RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations For The Location Of Fire And
Burglary Detection Devices Help Provide Proper Coverage For
The Protected Premises.

Recommendations For Smoke And Heat Detectors

With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72
noted below.

Early warning fire detection is best achieved by the installation of fire detection equipment
in all rooms and areas of the household as follows: For minimum protection a smoke detector
should be installed outside of each separate sleeping area, and on each additional floor of a
multi-floor family living unit, including basements. The installation of smoke detectors in
kitchens, attics (finished or unfinished), or in garages is not normally recommended.

For additional protection the NFPA recommends that you install  heat or smoke detectors  in
the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and
storage rooms, basements and attached garages.

In addition, we recommend the following:

Install a smoke detector inside every bedroom where a smoker sleeps.

• Install a smoke detector inside every bedroom where someone sleeps with the door partly

or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the
hallway outside may not wake up the sleeper if the door is closed.

• Install a smoke detector inside bedrooms where electrical appliances (such as portable

heaters, air conditioners or humidifiers) are used.

• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12

meters) long.

• Install smoke detectors in any room where an alarm control is located, or in any room

where alarm control connections to an AC source or phone lines are made. If detectors are
not so located, a fire within the room could prevent the control from reporting a fire or an
intrusion.

DINING

KITCHEN

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

BEDROOM

BDRM

BDRM

DINING 

LIVING ROOM

TV ROOM

KITCHEN

BEDROOM

BEDROOM

TO
BR

LVNG RM

BASEMENT

KTCHN

.

CLOSED
DOOR

GARAGE

Smoke Detectors for Minimum Protection

Smoke Detectors for Additional Protection

Heat-Activated Detectors

Recommendations For Proper Intrusion Protection

For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows
in a multi-level building.

In addition, we recommend that radio backup be used in a security system so that alarm signals can
still be sent to the alarm monitoring station in the event that the telephone lines are out of order
(alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).

Summary of Contents for 4110XM

Page 1: ...S E C U R I T Y S Y S T E M 4110XM N5478V5 7 96 Installation Instructions Installation Instructions Installation Instructions SEE INSIDE COVER FOR IMPORTANT NEW FEATURES AND INFORMATION Previous Menu...

Page 2: ...dom time delay up to 1 hour If AC is restored before the report goes out no report will be sent 6 Telephone number entries can now contain and a 2 second pause Enter 11 for Enter 12 for Enter 13 for 2...

Page 3: ...10 The Mechanics of Programming 10 Entering Program Mode 10 Programming a Data Field 10 Reviewing a Data Field 10 Erasing an Entry in a Data Field 10 Downloading 10 Clearing All Data Fields 10 Exiting...

Page 4: ...osed Smoke could be blocked by the closed door Also an alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical applianc...

Page 5: ...a 12VDC 2 AMP output assumes a fully charged 4AH battery is connected Steady output for Burglary Panic or pulsing output for Fire Output is current limited Communication Formats Ademco Low Speed Stan...

Page 6: ...eet Optional Keyswitch 4116 Keyswitch ZONE RESPONSE TYPE CHARACTERISTICS Zone Response Type Characteristics 0 Zone Disabled 1 Entry Exit Burglary Provides exit delay time when panel is armed in any ar...

Page 7: ...CABINET DOOR BOTTOM RETAINER CLIP RETAINER CLIP NOTE POSITION RETAINER SLOTS LOCKED UNLOCKED Figure 1 Installing The Cabinet Lock Mount the PC board either alone or with the wireless receiver in the...

Page 8: ...right OFF this equals address 0 as shown in Figure 4 4 3 2 1 ON OFF MOUNTING HOLES INTERFERENCE INDICATOR LED CIRCUIT BOARD DIP SWITCH PLUG SOCKET INSERT IN RIGHT HAND TERMINALS ANTENNAS YELLOW RED B...

Page 9: ...Telephone Line IMPORTANT Make sure telephones on the premises are connected only through the alarm control panel disconnect from the incoming phone line at the telephone jack This is necessary to have...

Page 10: ...numbers into the system see program fields 24 and 76 thru 92 Do not permanently mount transmitters until transmission from each location has been verified see Section 5 TESTING THE SYSTEM for instruct...

Page 11: ...viewing a Data Field Press plus Field No Note the following Data will be displayed for that field number entry by entry a beep will be heard between entries and three beeps after the last No changes w...

Page 12: ...TRY DELAY PERIMETER ARMED INTERIOR ARMED AWAY Security Code 2 Yes Yes Yes Yes STAY Security Code 3 Yes Yes Yes No INSTANT Security Code 7 Yes No Yes No MAXIMUM Security Code 4 Yes No Yes Yes DISARM Se...

Page 13: ...hen all tests are finished and verify results with them Transmitter ID Sniffer Mode 1 Enter Master Code 3 The following will occur The keypad will display all zone numbers of wireless units programmed...

Page 14: ...played 4a Interrupted AC power supply 4b Wire run from transformer to control is too long 4a Check transformer connection and power line circuit breaker 4b Make sure wiring run is not longer than the...

Page 15: ...plies with Part 68 of the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipme...

Page 16: ...e tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re n assure toutefois pas que le mat riel fonct...

Page 17: ...P 42 UP UP UP 43 UP UP 44 UP UP UP 45 UP UP 46 UP UP 47 UP 48 UP UP UP UP 49 U UP UP 50 UP UP UP 51 UP UP 52 UP UP UP 53 UP UP 54 UP UP 55 UP 56 UP UP UP 57 UP UP 58 UP UP 59 UP 60 UP UP 61 UP 62 UP 6...

Page 18: ...ors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their det...

Page 19: ...UIT BOARD HANDSET BLACK RED 1000 OHMS EOLR 1000 OHMS EOLR ZONE 1 ZONE 2 HI LO HI LO 1000 OHMS EOLR 1000 OHMS EOLR ZONE 3 ZONE 4 HI LO HI LO MAXIMUM LOOP RESISTANCE EACH ZONE 300 OHMS PLUS EOLR RESPONS...

Page 20: ...YONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE...

Reviews: