ADEMCO 4110XM Installation Instructions Manual Download Page 13

                         - 13-

   

Section 5.   TESTING THE SYSTEM

After installation is completed, the Security System should be carefully tested as follows:

Test Mode

1.

With the system disarmed, check that all zones are intact. If a N O T  READY  message
displays, press the  [

] key to display the faulted zone(s). Restore faulted zone(s) if necessary.

2.

Enter the [Security Code] +  [5] TEST.  The following will occur:

A test report will be transmitted (if programmed) to the Central Station immediately.  (If
the backup battery is discharged or missing, a LOW BATTERY report will be
transmitted with a TEST report.)

3.

Fault and restore each zone.

The keypad will emit 3 beeps each time a contact is faulted.

The keypad will beep once per minute as a reminder that the system is in the Test Mode.

4.

Exit this mode by entering the [Security  Code]  + [1]  OFF .

Armed System Test

Alarm messages will be sent to the central station during the following tests.  Notify them in
advance 
 that tests will be in progress.
1.

Arm the system and fault one or more zones.

2.

After 15 seconds (if optional dialer delay is selected), silence alarm sounder(s) by entering the
[Security Code]  +  [1] OFF.  Check Entry/Exit delay zones.

3.

Check the keypad-panic alarms that are in the system by pressing the Panic key (key pairs
on some keypads).

If the system has been programmed for audible emergency, the keypad will emit a steady
alarm sound, and ALARM and [Zone Number] will be displayed.  Silence the alarm by
entering the  [Security Code]  and pressing OFF.

If the system has been programmed for silent emergency, there will be no audible alarms
or displays, but a report will be sent to the central station.

4.

Notify the central station when all tests are finished, and verify results with them.

Transmitter ID Sniffer Mode

1.

Enter [Master Code] + [#] + [3].  The following will occur:

The keypad will display all zone numbers of wireless units programmed into the system.

2.

Fault and restore each transmitter.

As the system receives a signal from each of the transmitters, the zone number of that
trans mitter will disappear from the display.

After all wireless zones have transmitted a signal, none of the wireless zones should
remain on the display.  If any are still displayed, re-check DIP switch settings and
locations of the transmitters.

3.

Exit this mode by entering the  [Master Code] +  [1] OFF.

IMPORTANT

If the communicator is in the process of sending a report to the
central station, the system will not go into the Sniffer mode. If so, wait
a few minutes, and try again.

Go/No Go Test Mode

This test should be conducted to determine good mounting locations for transmitter. It verifies
that the RF transmission has sufficient signal amplitude margin for the installed system.  It is
similar to the regular Test mode (Code + [5] TEST), but the wireless receiver gain is reduced.
1.

Enter the [Master code] + [#] + [4].

2.

Follow steps 3 and 4 of the  Test Mode instructions described previously.

3.

Exit this mode by entering the [Master Code] + [1] OFF.

TO THE INSTALLER

Regular maintenance and inspection (at least annually) by the master and frequent testing by the user are vital
to continuous satisfactory operation of any alarm system.
The master should assume the responsibility of developing and offering a regular maintenance program to the
user as well as acquainting the user with the proper operation and limitations of the alarm system and its
component parts. Recommendations must be included for a specific program of frequent testing (at least weekly)
to insure the system's proper operation at all times.

Summary of Contents for 4110XM

Page 1: ...S E C U R I T Y S Y S T E M 4110XM N5478V5 7 96 Installation Instructions Installation Instructions Installation Instructions SEE INSIDE COVER FOR IMPORTANT NEW FEATURES AND INFORMATION Previous Menu...

Page 2: ...dom time delay up to 1 hour If AC is restored before the report goes out no report will be sent 6 Telephone number entries can now contain and a 2 second pause Enter 11 for Enter 12 for Enter 13 for 2...

Page 3: ...10 The Mechanics of Programming 10 Entering Program Mode 10 Programming a Data Field 10 Reviewing a Data Field 10 Erasing an Entry in a Data Field 10 Downloading 10 Clearing All Data Fields 10 Exiting...

Page 4: ...osed Smoke could be blocked by the closed door Also an alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical applianc...

Page 5: ...a 12VDC 2 AMP output assumes a fully charged 4AH battery is connected Steady output for Burglary Panic or pulsing output for Fire Output is current limited Communication Formats Ademco Low Speed Stan...

Page 6: ...eet Optional Keyswitch 4116 Keyswitch ZONE RESPONSE TYPE CHARACTERISTICS Zone Response Type Characteristics 0 Zone Disabled 1 Entry Exit Burglary Provides exit delay time when panel is armed in any ar...

Page 7: ...CABINET DOOR BOTTOM RETAINER CLIP RETAINER CLIP NOTE POSITION RETAINER SLOTS LOCKED UNLOCKED Figure 1 Installing The Cabinet Lock Mount the PC board either alone or with the wireless receiver in the...

Page 8: ...right OFF this equals address 0 as shown in Figure 4 4 3 2 1 ON OFF MOUNTING HOLES INTERFERENCE INDICATOR LED CIRCUIT BOARD DIP SWITCH PLUG SOCKET INSERT IN RIGHT HAND TERMINALS ANTENNAS YELLOW RED B...

Page 9: ...Telephone Line IMPORTANT Make sure telephones on the premises are connected only through the alarm control panel disconnect from the incoming phone line at the telephone jack This is necessary to have...

Page 10: ...numbers into the system see program fields 24 and 76 thru 92 Do not permanently mount transmitters until transmission from each location has been verified see Section 5 TESTING THE SYSTEM for instruct...

Page 11: ...viewing a Data Field Press plus Field No Note the following Data will be displayed for that field number entry by entry a beep will be heard between entries and three beeps after the last No changes w...

Page 12: ...TRY DELAY PERIMETER ARMED INTERIOR ARMED AWAY Security Code 2 Yes Yes Yes Yes STAY Security Code 3 Yes Yes Yes No INSTANT Security Code 7 Yes No Yes No MAXIMUM Security Code 4 Yes No Yes Yes DISARM Se...

Page 13: ...hen all tests are finished and verify results with them Transmitter ID Sniffer Mode 1 Enter Master Code 3 The following will occur The keypad will display all zone numbers of wireless units programmed...

Page 14: ...played 4a Interrupted AC power supply 4b Wire run from transformer to control is too long 4a Check transformer connection and power line circuit breaker 4b Make sure wiring run is not longer than the...

Page 15: ...plies with Part 68 of the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipme...

Page 16: ...e tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re n assure toutefois pas que le mat riel fonct...

Page 17: ...P 42 UP UP UP 43 UP UP 44 UP UP UP 45 UP UP 46 UP UP 47 UP 48 UP UP UP UP 49 U UP UP 50 UP UP UP 51 UP UP 52 UP UP UP 53 UP UP 54 UP UP 55 UP 56 UP UP UP 57 UP UP 58 UP UP 59 UP 60 UP UP 61 UP 62 UP 6...

Page 18: ...ors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their det...

Page 19: ...UIT BOARD HANDSET BLACK RED 1000 OHMS EOLR 1000 OHMS EOLR ZONE 1 ZONE 2 HI LO HI LO 1000 OHMS EOLR 1000 OHMS EOLR ZONE 3 ZONE 4 HI LO HI LO MAXIMUM LOOP RESISTANCE EACH ZONE 300 OHMS PLUS EOLR RESPONS...

Page 20: ...YONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE...

Reviews: