SECTION 16: S
PECIFICATIONS
57 of 59
16.2 General Technical Data Table
Model
UHA[T][X][S]
150
UHA[T][X][S]
175
UHA[T][X][S]
200
UHA[T][X][S]
225
UHA[T][X][S]
250
Full Load Amps @ 120 V
A
10.6
10.6
10.6
10.6
10.6
Air Volume
CFM
3500
3500
3716
3716
3716
Flue and Air Intake
Flue Intake Size
in (cm)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
Air Intake Size
in (cm)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
*Maximum Straight
Flue/Air Intake
ft (m)
40 (1)
40 (1)
40 (1)
40 (1)
40 (1)
Weight (Net)
lbs
(kg)
217
(98.4)
237
(107.5)
255
(115.7)
265
(120.2)
270
(122.5)
*Do not exceed the maximum length of flue stated or heater may not operate properly.
16.3 Technical Data Table
Model
UHA[T][X][S]
150
UHA[T][X][S]
175
UHA[T][X][S]
200
UHA[T][X][S]
225
UHA[T][X][S]
250
Total Input
(Btu/h) x (1000)
150
175
200
225
250
Total Output
(Btu/h) x (1000)
123
143.5
164
184.5
205
Total Output Low Fire
(Btu/h) x (1000)
86
100
115
129
143.5
Efficiency (Max Input)
%
82
82
82
82
82
Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressure
in wc
2.9
3.0
3.2
3.4
3.45
Burner Pressure Low Fire
in wc
1.3
1.3
1.6
1.7
1.7
LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressure
in wc
11
11.3
9.5
11.1
11.6
Burner Pressure Low Fire
in wc
5.0
5.5
4.7
5.4
5.5
Summary of Contents for UHAS 150
Page 2: ......
Page 4: ......
Page 8: ......
Page 48: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 40 of 59 14 1 General...
Page 68: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 60 of 59...
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......