CHAPTER 4
Using the Gateway
182
“Sensor Tables” for conversion/linearization; if you intend to
use a linear sensor, select “none”;
Figure 193. Sensor type - Conversion settings - Sensor table - Analog
Note: If a sensor table is entered for a non-linear sensor, the fol-
lowing entries for Linear input value refer to the output val-
ues of the linearization table and not to the voltage
measured on the analog pin!
•
Linear input value - entry of the minimum and maximum value
of the range within which the sensor delivers measurements;
Note: Due to its linear characteristic, a linear sensor is by default
exactly defined by only two input values, the minimum and
the maximum. The range for analog sensors is 0 - 2.5 Volts.
•
Linear output value - entry of the minimum and maximum
value of the linear output range which has to correspond to
the linear input value range, in the engineering units which
have been selected;
Note: For example, in Fig. 189, the input range of
0 - 2,5 Volts cor-
responds to the output range of 0 - 120 km/h wind speed.
•
Verifier - entry of the minimum and maximum value within
which valid sensor measurement results can be expected. If
the values are outside the preset thresholds, an invalid sensor
value will be notified;
•
Display scale - enter the minimum and maximum value for
scaling which should to be displayed on the trend graph
“Sensor data graphic”.
Counter sensor types
The “Sensor type” window provides the following window areas
for counter sensor types:
•
Common settings - for entering the common definitions of the
sensor type, especially determining its technology;
Summary of Contents for A850
Page 92: ...CHAPTER 3 Configuring the Gateway 92 Figure 81 PPP Configuration Window ...
Page 128: ...CHAPTER 3 Configuring the Gateway 128 Figure 132 Dialup Modem Window ...
Page 164: ...CHAPTER 3 Configuring the Gateway 164 ...
Page 177: ...CHAPTER 4 Sensor Type Configuration 177 Figure 183 Sensor type Window Analog ...
Page 196: ...CHAPTER 4 Using the Gateway 196 Figure 216 Sensor type Window LC ...
Page 200: ...CHAPTER 4 Using the Gateway 200 Figure 222 Sensor type Window OC ...
Page 204: ...CHAPTER 4 Using the Gateway 204 Figure 228 Sensor type Window SDI ...
Page 215: ...CHAPTER 4 Logs 215 Figure 241 System Log Selection Log types Figure 242 System Log Log types ...
Page 275: ...CHAPTER 4 RTU Network Configuration 275 Sensor details Figure 319 Sensor details Window ...
Page 366: ...CHAPTER 6 Appendix 366 ...