Installing Multiplexers
800-357-104-01, Revision 01
34
September 29, 2000
HMS-357 List 4 and List 5
HX
U
-3
5
7
After initial installation, the HXU-357 multiplexer unit must be configured properly or continuous alarms will
occur when the DS1 interface is placed in operation mode. During installation, the DS1 interface should be
configured as Out-of-Service and Unequipped (Maintenance mode). The DS3 interface is configured as
Out-of-Service.
Setting Up the Communications Channel through the HXU-357
The AUX port is not available to the user as a craft interface when any multiplexer is used in the shelf. HMU-319
List 7A automatically sets up the AUX port when the IP address is assigned to support IP network communication
with the HXU-357.
These settings do not effect the transmitted payload, they only suppress the alarms and allow for
modification.
Step
Procedure
Installer Check
ü
ü
ü
ü
The following procedure assumes proper TAO login.
For proper login procedure, please refer to
“Using the Terminal Access Option” on
1
From the Network Status screen, enter the number of the desired shelf ID (1 through 32), and then
press .
H
2
From the Shelf Status screen, press
to select Shelf Options.
H
3
From the Shelf Options screen, press
to configure the Mux Type.
H
4
Press
for HXU-357.
H
5
Enter the assigned IP address for the HXU-357.
For more information on IP addressing, refer to
“Network Specifications” on page 75
H
When using an HXU-357, a 10BASE-T module (ADC part number 150-2233-01) is
necessary for network management.
6
Press
to exit the screen, then press
to confirm and save the setting and return to the root
menu of the Shelf Status screen.
H
7
Proceed to
“Setting Up Basic HXU-357 System Parameters in the System Administration Menu” on
.
H