INSTALLATION IN WET ROOMS
INSTALLATION IN WET ROOMS
INSTALLATION IN WET ROOMS
INSTALLATION IN WET ROOMS
For installations in wet rooms specific installation guidelines apply, which are to be seen in the context of placing the
power adapter outside of certain protection zones. These regulations differ by region. Please contact a specialist for
this. In Germany electrical installations are to be performed by a skilled technician, while observing the regulations of
the standard DIN VDE 0100 T.701.
According to this standard, ad notam monitor systems with DC 12V (Limited Power Source Class II, SELV) can be
installed at each position (incl. Zones “0” and “1”) in harsh environments, also in showers and above a bath tub as
long as the monitor system is shielded from a sealed glass surface and the (external) power adapter is installed
beyond these protection zones.
NOTE
NOTE
NOTE
NOTE
The safety current source has to be arranged outside the zones 0 - 2 and needs to be protected against direct impact.
The assessment of the protection zones on site of the installation must be performed in accordance with the
12
valid national guidelines by a skilled local electrician. ad notam will not be held liable for improper installation!
SMART DISPLAY UNIT
TM
Zone
Class
Requirements
0
IP x6-8
waterproof, max. 12V,
only SELV qualified electronic devices
1
IP x5
hose waterproof, max. 50V,
only stationary electronic devices
(IP x5 or qualified SELV)
2
IP x4
splashproof,
only stationary electronic devices
(IP x4 or qualified SELV)
3
IP x0-3
devices with at least protection against
dripping water recommended