5.8.4
Roof outlet prefabricated chimney
Appliance category: C33
When there is little space in a shaft, a roof outlet through a prefabricated chimney
may be necessary.
The prefabricated chimney must comply with the minimum lengths shown. The
supplier must guarantee the proper operation of the prefabricated chimney with
respect to wind attack, ice formation, rain ingress, etc.
In view of the different models and requirements, the prefabricated chimneys must be
adjusted to the local situation: a gas certificate is not required
VOORZICHTIG
CAUTION
The connection of the air supply and the flue discharge
between the appliance and the prefab chimney must be made
in pipes of diameter 80 mm.
Permitted pipe lengths
Air supply and combustion gas flue pipe (together).
Kompak HRE eco 12 and 18 Solo
105 meters
Kompak HRE eco 30 Solo
85 meters
Kompak HRE eco 40 Solo
65 meters
Combustion gas flue and air supply pipe
For assembly see section 5.8 Assembly general
Mounting of prefabricated chimney
The outlet can be made at any place in the pitched or flat roof surface