Changing the MCBA settings: Parameter mode

Proceed as follows:
• 

Press the “MODE” button once; the display will show “PARA”.
Press the “STEP” button once; the first digit is “1” and the last
two show the setting for the first parameter.

• 

To change these last two, press “+” to increase and “-” to decrease.

• 

Save the new setting selected with the “STORE” button.

• 

To access the next parameter, press “STEP”.

• 

Press the “MODE” button twice to return to standby mode.

List of accessible parameters:

Temperature measurement display: Info mode

Proceed as follows:
• 

Press the “MODE” button twice; the display will show “INFO”.

• 

Press the “STEP” button once; the first digit is the measurement
number and the last two its value.

• 

Press the “STEP” button to display the next measurement.

• 

To return to standby mode, press the “MODE” button once.

List of measurements available:

16

USER GUIDE

Parameter N°

1

2

3

4

Range

20 - 90 °C

O = OFF; 1 = ON

O = OFF; 1 = ON

60 - 90 °C

Description

hot water setting

“Hot water” system status

“Heating” system status

Heating setting

Measurement N°

1

2

3

4

5

6

7

8

9

Description

Temperature T1 - primary

Temperature T2 - primary

Temperature T3 - secondary

-

-

Setting for T1

Variation of T1 - °C/s

Variation of T2 - °C/s

Variation of T3 - °C/s

0

0

8

CONTROL SETTINGS

The boiler is controlled by the MCBA (microprocessor), with the
control panel housed behind a flap on the front of the boiler - see
picture on page 16.

Standby Mode

Standby Mode is the normal operation display setting.

The first digit shows the boiler sequence. This sequence relates to
current boiler status. The last two digits show the boiler temperature.

If the burner is turned off because of an extra protection, the display
shows boiler-sequence 9 and the flow-temperature. This alternates
with the error code eg. b26.

Sequence

0

1

2

3

4

5

6

7

8

9

A

G

H

L

t

Boiler status

Stand By, no heat request

Pre-purge, post-purge

Ignition

Burning in CH-mode

Burning in DHW-mode

Waiting for opening of Air pressure switch (max. 1 Min.)

Waiting for closing of Air pressure switch (max. 2 x 1 Min.)

Burner off because the set-value has been reached

Overrun time pump in CH-mode

Overrun time pump in DHW-mode

Burner off because of protection:

(automatic restart occurs when the condition has cleared)

• “b08”: airflowsensor did not close

• “b18”: T1 > 95 °C

• “b19”: T2 > 95 °C

• “b24”: T2 - T1 > 10,20 or 40 °C after 19 minutes

• “b25”: dT1/dt > Maximum Gradient T1

• “b26”: Minimum gas pressure switch not closed

• “b28”: no fan signal

• “b29”: fan signal, incorrect fan rotation

• “b30”: T1 - T2 > Max. delta

• “b33”: NTC3 short circuit

• “b35”: NTC5 short circuit

• “b38”: NTC3 open circuit

• “b40”: NTC5 open circuit

• “b52”: T5 > T5max

• “b61”: airflowsensor closed

• “b65”: wait for fanstart

Internal control

Burner on for holding boiler warm

Burner-high function: Testmode max. RPM in CH-mode

Burner-low function: Testmode min. RPM in CH-mode

Burner on for manual fanspeed (servicing)

Summary of Contents for HM 71

Page 1: ...er tube is coated with metal fibre NIT which in addition to its remarkable heat exchange capabilities gives greater durability The main components are a venturi and one model 71 or two model 101 gas v...

Page 2: ...w m3 h 2 46 8 60 3 80 13 17 Gas G31 37 50 mbar I 3P Flow m3 h 0 82 2 86 0 94 4 50 Pressure drop combustion chamber mbar 0 6 1 4 Flue gas temperature net C 172 165 Mass flow rate of combustion products...

Page 3: ...rn OFF the on off switch on the boiler control panel and isolate external electrical supply 2 Turn off the gas supply to the boiler 3 Remove the flue to gain access to the top of the boiler 4 Remove t...

Page 4: ...our installer will have informed you of this value at the time of installation see Commissioning Section Filling the hot water and heating circuits If the pressure falls below 1 bar the boiler water p...

Page 5: ...behind a flap on the front of the boiler see picture on page 16 Standby Mode Standby Mode is the normal operation display setting The first digit shows the boiler sequence This sequence relates to cu...

Page 6: ...ck that sensor NTC2 is propely housed in its pocket if so change sensor NTC2 check that the shunt pump is operating and if so vent the boiler if the fan is turning check the PWM connection if the prob...

Page 7: ...Efficiency Gas pressure SERVICE RECORD Date serviced CO2 min load CO2 max load Gas LPG Remarks Name and signature Flue gas T Efficiency Gas pressure Date serviced CO2 min load CO2 max load Gas LPG Re...

Page 8: ...84 E MAIL sales triangletube com ARGENTINA TECNOPRACTICA ALFEREZ BOUCHARD 4857 1605 CARAPACHAY BUENOS AIRES TEL 54 11 47 65 33 35 FAX 54 11 47 65 43 07 E MAIL jchas tecnopractica com BRAZIL SIMETAL IN...