TECHNICAL CHARACTERISTICS
BOILER ROOM
- make sure that all air vents are unobstructed at all times.
- do not store any flammable products in the boiler room.
- do not store any corrosive products, paint, solvents, salts, chloride
products and other detergent products near the appliance.
- if you smell gas, do not switch on or off any lights, turn off the gas
meter, ventilate the rooms and contact your installer.
- The base on which the boiler rests must be made of non-combustible
materials.
CHIMNEY CONNECTION
- Chimney connection must comply with the applicable standards (NBN
D51-003 in Belgium), and take into account the local requirements
of the energy provider, the fire requirements and the regulation on
"noise pollution".
- The flue pipe size must not be smaller than the size of the boiler outlet
connection
B23 and B23P type chimney connection
The boiler is connected to the chimney by a metal pipe rising at an angle
from the boiler to the chimney. A flue disconnection piece is required.
It must be easily removable to give access to the flue pipes when
performing boiler maintenance.
Due to the high efficiency of our boilers, the flue gases exit at a low
temperature. Accordingly, there is a risk for the flue gases to condense,
which could damage the chimney and the boiler. Therefore, it is strongly
recommended to line the chimney.
`
Minimum supply of fresh air into
the boiler room
Fresh air supply
High
Low
(B23 and B23P)
HeatMaster® 30N
cm
2
≥ 150
≥ 200
HeatMaster® 60N
cm
2
≥ 150
≥ 200
HeatMaster® 70 N
cm
2
≥ 150
≥ 200
HeatMaster® 100N
cm
2
≥ 210
≥ 320
Dimensions of a B23 type chimney
Height
5 m
10 m
15 m
HeatMaster® 30N
Ø mm
150
150
150
HeatMaster® 60N
Ø mm
189
159
150
HeatMaster® 70 N
Ø mm
189
159
150
HeatMaster® 100N
Ø mm
234
178
150
Note:
Given that regulations vary from one country to another,
the table above is given by way of indication only.
MAXIMUM OPERATING CONDITIONS
Maximum Service Pressure (DHW tank full of water)
- Primary circuit
3 bar
- DHW circuit
10 bar
Maximum Test Pressure (DHW tank full of water)
- Primary circuit
4.5 bar
- DHW circuit
13 bar
Maximum Operating Conditions
- Maximum temperature of primary fluid 90 °C
- Minimum temperature of primary fluid 60 °C
Water Quality
• Chlorides ≤ 150 mg/l (304)
• 6 ≤ pH ≤ 8
CHIMNEY CONNECTION CHARACTERISTICS
HEATMASTER® WITHOUT BURNER
HeatMaster®
30 N
HeatMaster®
60 N
HeatMaster®
70 N
HeatMaster®
100 N
Volume of the combustion chamber
m
3
0.051
0.051
0.075
0.075
Mass flow rate of combustion products
g/s
15.2
30.6
30.6
46.9
Max. pressure drop in flue pipe
Pa
1
60
60
140
Flue pipe diameter
mm
150
150
150
150
Net temperature
°C
180
195
170
170
B23
✔
✔
✔
✔
HEATMASTER® PROVIDED WITH AN ACV BG 2000-S BURNER
HeatMaster®
30 N
+ BG 2000-S / 35
HeatMaster®
60 N
+ BG 2000-S / 60
HeatMaster®
70 N
+ BG 2000-S / 70
HeatMaster®
100 N
+ BG 2000-S / 100
Mass flow rate of combustion products
g/sec.
16.0
32.1
32.1
51.4
Net temperature
°C
163
186
172
165
B23
✔
✔
✔
✔
B23P
✔
✔
✔
✔
C13
✔
✔
✔
✔
C33(x)
✔
✔
✔
✔
C53(x)
✔
✔
✔
✔
C63(x) - only in Germany and Luxemburg
✔
Summary of Contents for HeatMaster 100 N
Page 16: ...EN FR RU PL DE IT ES NL EN 15 664Y5400 B INSTALLATION 2 x 1 2 3 4 5 6...
Page 21: ...EN FR RU PL DE IT ES NL EN 20 664Y5400 B...
Page 22: ...EN FR RU PL DE IT ES NL EN 21 664Y5400 B...
Page 23: ...EN FR RU PL DE IT ES NL EN 22 664Y5400 B...
Page 24: ...EN FR RU PL DE IT ES NL EN 23 664Y5400 B...
Page 25: ......
Page 26: ......
Page 27: ......