TECHNICAL CHARACTERISTICS

BOILER ROOM

-   make sure that all air vents are unobstructed at all times.

-   do not store any flammable products in the boiler room.

-   do not store any corrosive products, paint, solvents, salts, chloride 

products and other detergent products near the appliance.

-   if you smell gas, do not switch on or off any lights, turn off the gas 

meter, ventilate the rooms and contact your installer.

-   The base on which the boiler rests must be made of non-combustible 

materials.

CHIMNEY CONNECTION

-   Chimney connection must comply with the applicable standards (NBN 

D51-003 in Belgium), and take into account the local  requirements 

of the energy provider, the fire requirements and the regulation on 

"noise pollution". 

-  The flue pipe size must not be smaller than the size of the boiler outlet 

connection

B23 and B23P type chimney connection

The boiler is connected to the chimney by a metal pipe rising at an angle 

from the boiler to the chimney. A flue disconnection piece is required. 

It must be easily removable to give access to the flue pipes when 

performing boiler maintenance. 

Due to the high efficiency of our boilers, the flue gases exit at a low 

temperature. Accordingly, there is a risk for the flue gases to condense, 

which could damage the chimney and the boiler. Therefore, it is strongly 

recommended to line the chimney.

`

Minimum supply of fresh air into 

the boiler room

Fresh air supply

High

Low

(B23 and B23P)

HeatMaster® 30N

cm

2

≥ 150

≥ 200

HeatMaster® 60N

cm

2

≥ 150

≥ 200

HeatMaster® 70 N

cm

2

≥ 150

≥ 200

HeatMaster® 100N

cm

2

≥ 210

≥ 320

Dimensions of a B23 type chimney

Height

5 m

10 m

15 m

HeatMaster® 30N

Ø mm

150

150

150

HeatMaster® 60N

Ø mm

189

159

150

HeatMaster® 70 N

Ø mm

189

159

150

HeatMaster® 100N

Ø mm

234

178

150

 Note:

 

Given that regulations vary from one country to another, 

the table above is given by way of indication only.

MAXIMUM OPERATING CONDITIONS

Maximum Service Pressure (DHW tank full of water)

- Primary circuit 

3 bar

- DHW circuit 

10 bar

Maximum Test Pressure (DHW tank full of water)

- Primary circuit 

4.5 bar

- DHW circuit 

13 bar

Maximum Operating Conditions

- Maximum temperature of primary fluid  90 °C

- Minimum temperature of primary fluid  60 °C

Water Quality

• Chlorides ≤ 150 mg/l (304)

• 6 ≤ pH ≤ 8

CHIMNEY CONNECTION CHARACTERISTICS

HEATMASTER® WITHOUT BURNER

HeatMaster® 

30 N

HeatMaster® 

60 N

HeatMaster® 

70 N

HeatMaster® 

100 N

Volume of the combustion chamber

m

3

0.051

0.051

0.075

0.075

Mass flow rate of combustion products

g/s

15.2

30.6

30.6

46.9

Max. pressure drop in flue pipe

Pa

1

60

60

140

Flue pipe diameter

mm

150

150

150

150

Net temperature

°C

180

195

170

170

B23

HEATMASTER® PROVIDED WITH AN ACV BG 2000-S BURNER

HeatMaster® 

30 N

+ BG 2000-S / 35

HeatMaster® 

60 N

+ BG 2000-S / 60

HeatMaster® 

70 N

+ BG 2000-S / 70

HeatMaster® 

100 N

+ BG 2000-S / 100

Mass flow rate of combustion products

g/sec.

16.0

32.1

32.1

51.4

Net temperature

°C

163

186

172

165

B23

B23P

C13

C33(x)

C53(x)

C63(x) - only in Germany and Luxemburg

Summary of Contents for HeatMaster 100 N

Page 1: ...EN FR RU PL DE IT ES NL EN 1 664Y5400 B INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS HeatMaster 30 N 60 N 70 N 100 N...

Page 2: ...E ES IT PL RU M M L1 N PE P t t t 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 P 1 2 C 2 1 3 1 5 4 2 t C 2 1 t C 2 1 3 2 1 5 11 10 12 13 9 15 16 14 8 7 6 4 Br B Br Br O G B B B B B B B B B Y Gr...

Page 3: ...ctrical Characteristics 13 INSTALLATION 14 Package Contents 14 Boiler Preparation 14 DHW Connection 16 Heating Connection 17 STARTING UP 18 Filling the DHW and Heating Circuits 18 Starting up the Boil...

Page 4: ...s and features of its products without prior notice The availability of certain models as well as their accessories may vary according to markets WARNINGS RECOMMENDATIONS Please carefully read this ma...

Page 5: ...pencil or similar pointed device then reinstall the cap If the fault persists turn the boiler off and call a service engineer Daily timer Allows the HeatMaster to be turned on and off at specific mome...

Page 6: ...g valve Safety valves If water discharges from any of the safety valves turn the boiler off and call a service engineer BURNER SAFETY MECHANISM SAFETY CUTOUT OF THE OIL OR GAS BURNER HeatMaster 30 N T...

Page 7: ...Heating circuit outlet 14 Domestic hot water outlet 15 Stainless steel Tank in Tank hot water production tank 16 Flue pipes and turbulators 17 Primary circuit 18 Heating circuit return 19 Combustion c...

Page 8: ...tlet 14 Domestic hot water outlet 15 Stainless steel Tank in Tank hot water production tank 16 Flue pipes and turbulators 17 Primary circuit 18 Heating circuit return 19 Combustion chamber 20 Oil burn...

Page 9: ...390 1619 1382 284 126 HeatMaster 30 N 60 N 310 340 680 1728 HM 70 N 2128 HM 100 N 1743 HM 70 N 2093 HM 100 N 340 342 428 831 678 390 1613 HM 100 N 285 127 1641 HM 70 N 2045 HM 100 N HeatMaster 70 N 10...

Page 10: ...d Minimum A mm 650 500 B mm 800 700 C mm 500 300 D mm 300 250 E mm 150 100 F mm 800 700 C A B D C A B E F C B C A B E F E F BURNER CHAMBER PLATE The burner chamber plate has four threaded holes M8 to...

Page 11: ...nection F 1 1 2 1 1 2 1 1 2 1 1 2 DHW Connection M 3 4 3 4 1 1 DHW tank heat exchanger surface m2 2 46 2 46 3 14 3 95 Primary circuit water pressure drop T 20K mbar 27 54 46 83 Total capacity L 162 16...

Page 12: ...Minimum supply of fresh air into the boiler room Fresh air supply High Low B23 and B23P HeatMaster 30N cm2 150 200 HeatMaster 60N cm2 150 200 HeatMaster 70 N cm2 150 200 HeatMaster 100N cm2 210 320 D...

Page 13: ...150 1m straight pipe 6 1 6 2 90 elbow 15 2 15 5 45 elbow 6 1 6 2 Condensate recovery container _ 2 _ 4 Terminal 20 10 20 20 This table is based on ACV equipment and cannot be applied as a rule In the...

Page 14: ...high limit thermostat 5 Low primary water pressure indicator 6 Low water pressure switch 7 Daily timer 8 Summer winter switch 9 Burner safety cutout warning indicator 10 Room temperature option 11 He...

Page 15: ...wrapped in a plastic film At product reception and after removal of packaging check the package contents and that the appliance is free of damages Contents A HeatMaster N boiler Installation operation...

Page 16: ...EN FR RU PL DE IT ES NL EN 15 664Y5400 B INSTALLATION 2 x 1 2 3 4 5 6...

Page 17: ...peratures in excess of 60 C which can cause burns ACV therefore recommends that you install a thermostatic mixing valve immediately after the appliance outlet If stop valves are used in the domestic h...

Page 18: ...ly If the heating system is connected to the primary circuit calculate the expansion capacity necessary for the total volume of the heating system refer to the technical instructions from a relevant m...

Page 19: ...ntil you reach an approximate pressure of 1 5 bar in the system 4 Bleed the boiler and the whole system using the automatic air bleed valve located on top of the appliance STARTING UP THE BOILER START...

Page 20: ...devices are working properly Test the safety valves on the central heating and hot water circuits SERVICING THE BURNER Forallburners pleaserefertotherelevantservicingandtroubleshooting instructions i...

Page 21: ...EN FR RU PL DE IT ES NL EN 20 664Y5400 B...

Page 22: ...EN FR RU PL DE IT ES NL EN 21 664Y5400 B...

Page 23: ...EN FR RU PL DE IT ES NL EN 22 664Y5400 B...

Page 24: ...EN FR RU PL DE IT ES NL EN 23 664Y5400 B...

Page 25: ......

Page 26: ......

Page 27: ......

Reviews: