Total capacity
L
318
413
606
Primary capacity
L
55
55
161
Heating surface area
m
2
2.65
3.24
3.58
Primary pressure drop
mbar
90
95
92
Primary flow rate
Ltrs/hr
6200
6400
7200
Maximum useable input from boiler
kW
73
88
88
Primary connections (female BSP)
Ø
1
1/2
"
1
1/2
"
2"
Hot water connections (male BSP)
Ø
1
1/2
"
1
1/2
"
1
1/2
"
Weight empty
kg
141
167
238
Weight full
kg
459
580
844
Maximum operating temperature
°C
90
90
90
High efficiency hot water storage
7
Technical Data
Performance Data
SmartLine SL
High efficiency hot water storage
6
Fast recovery Tank-in-Tank
cylinder – perfect partner to
condensing boiler.
At a time when consumers are demanding higher performance from
their hot water installations, the traditional coil based cylinders find it
more difficult to deliver high volumes of water for the modern user.
ACV Tank-in-Tank technology represents a significant advance in the
science of hot water production.
A greater heat transfer surface means Tank-in-Tank units recover much
faster than any other type of hot water storage cylinder – keeping
boiler cycling to a minimum, and ultimately giving improved fuel
efficiency with outstanding hot water delivery.
SmartLine SL Features:
• Stainless steel construction –
no anode protection required
• Low heat loss –
high quality 50mm polyurethane insulation
• Easy access control pod with thermostats and six-pin plug for
simple electrical connection
• Hard wearing polypropylene finish
• Vented or unvented use
• Mains pressure SystemPak available
• Residential or commercial use
• Can be used in battery formation for higher
hot water output
SL320
SL420
SL600
Litres in first 10 minutes
40°C
922
1195
1345
Litres in first 10 minutes
45°C
790
1012
1153
Litres in first 10 minutes
60°C
504
620
706
Litres in first hour
40°C
2666
3151
3437
Litres in first hour
45°C
2285
2608
2946
Litres in first hour
60°C
1368
1513
1733
Continuous flow 40°C
Ltrs/hr
2093
2536
2511
Continuous flow 45°C
Ltrs/hr
1794
2058
2152
Continuous flow 60°C
Ltrs/hr
1037
1153
1232
Initial heat up time 10°C to 85°C
Min
23
24
35
C
B
A
135
D
135
135
SL320
SL420
SL600
A
1593mm
2018mm
1892mm
B
1280mm
1705mm
1583mm
C
250mm
250mm
255mm
D
660mm
660mm
817mm
1
2
3
4
5
6
7
8
9
10
11
12
1.
DHW return or temp/
pressure relief valve
2.
Cold feed
3.
Insulation 50mm
4.
Primary hot water flow
5.
DHW tank
6.
Primary return
7.
Primary hot water
8.
Air vent
9.
DHW flow
10. Rigid top case
11. Stain resistant jacket
12. Rigid base
Characteristics
Dimensions
Please Note:
Performance data assumes a primary flow temperature of 85°C and a domestic cold water supply of 10°C without the use of a thermostatic
mixing valve on the domestic hot water outlet.
Maximum operating pressure Primary: 4 bar Secondary: 10 bar