8
1
5
7
11
12
9
3
4
2
10
6
High efficiency combination boilers
17
Technical Data
Performance Data
HeatMaster® 60
High performance, combined
direct fired boiler and water heater.
Can also be used as a stand alone
water heater.
Simple, Well Proven Performance
At the heart of the HeatMaster is a stainless steel cylinder through which
the flue tubes pass. This is surrounded by a mild steel shell containing
the primary water.
The outer shell extends down to the combustion chamber and around
the flue tubes. The heat transfer surface is therefore much greater than
that of standard direct fired water heater. A circulating pump fitted to
the primary circuit moves the water around the tank, heating it faster
and maintaining an even temperature across the primary jacket.
The burner fires into the combustion chamber which indirectly heats the
stainless steel cylinder containing the DHW. As with all Tank-in-Tanks,
this is corrugated over its full height and suspended in the HeatMaster
by its hot and cold water connections.
It is capable of operating at very high temperatures.
Key Benefits
• Limescale build up is prevented because the:
- cylinder expands and contracts during use
- cold water does not come into contact with
the intense heat of the burner flame
•
No need for sacrificial anodes due to:
- scale resistant features
- corrosion resistance of stainless steel
•
The HeatMaster has one very major advantage over other direct fired
water heaters
- because it heats the DHW with a primary circuit, this primary water
can be used to provide central heating as well
• Most hot water and heating demands can be met - simply by
connecting two, three, four or more HeatMasters together in a
module.
• The HeatMaster range can be used in conjunction with SL and Jumbo
hot water storage tanks – supplying even the largest hot water
requirement.
High efficiency combination boilers
16
Combined temperature
and pressure gauge
Control
thermostat
Time clock
Manual reset high
limit thermostat
ON / OFF
switch
Summer /
Winter switch
HeatMaster®60
HeatMaster®60
Fuel
Oil (28 sec or 35 sec)
Natural gas/LPG
Burner options
type
Pressure Jet
BG2000-S or forced draught
Input
kW
69.9
69.9
Maximum output
kW
62.5
62.9
Primary capacity
L
82
82
Total capacity
L
162
162
Heating surface area
m
2
2.46
2.46
Primary circuit pressure drop
mbar
54
54
DHW tank pressure drop
mbar
45
45
Flue circuit pressure drop
mbar
0.6
0.6
DHW connection (male BSP)
Ø
3/4
"
3/4
"
Primary connection (female BSP)
Ø
1
1/2
"
1
1/2
"
Flue connection (G)
Ø mm
150
150
Flue connection options
type
B23
B23/C13/C33/C53
BG2000 air intake connection
Ø mm
n/a
80
Weight empty
Kg
220
220
Weight full
Kg
382
382
Minimum working gas pressure
mbar
n/a
20(Nat Gas)/37(LPG)
Gas flow rate
m
3
/h
n/a
7.40(Nat Gas/2.86(LPG)
Maximum operating temperature
°C
90
90
Maximum operating pressure Primary: 3 bar Secondary: 10 bar
Gas connection - BG2000 S/60:
3/4
"
II
O
O
Manual reset high
limit thermostat
Low water
pressure switch
Primary safety
valve
Control
thermostat
Thermal reset high
limit thermostat
1. Stainless steel inner tank
2. Primary heating circuit
3. Flue pipes with stainless
steel turbulators
4. Rigid polyurethane
foam insulation
5. Primary shunt pump
6. Combustion chamber
7. Oil or gas burner
8. Control panel
9. Primary water flow
connection
10. Primary water return connection
11. Domestic cold water inlet
12. Domestic hot water outlet
HeatMaster®60
Litres in first 10 minutes
40°C
474
Litres in first 10 minutes
45°C
378
Litres in first 10 minutes
60°C
245
Litres in first hour
40°C
1942
Litres in first hour
45°C
1656
Litres in first hour
60°C
1106
Continuous flow 40°C
Ltrs/hr
1835
Continuous flow 45°C
Ltrs/hr
1573
Continuous flow 60°C
Ltrs/hr
1101
Reheat time to 60°C
Min
9
HeatMaster®60 Oil
HeatMaster®60 Gas/LPG
A
1698mm
1698mm
B
1583mm
1583mm
C
538mm
538mm
D
791mm
801mm (BG2000)
E
540mm
540mm
F
390mm
390mm
G
150mm
150mm
H
1098mm
1098mm
J
281mm
281mm
Characteristics