High efficiency combination boilers
29
Technical Data
Delta Pro
High efficiency combination boilers
28
Performance Data
Dimensions
Delta Pro 25
Delta Pro 45
Delta Pro 55
Input power [input]
kW
27.9
50.0
61.0
Useful nominal power [output]
kW
26.0
45.0
55.0
Efficiency
%
89.6
90
90.1
Total capacity
L
158
127.5
151
Primary capacity
L
83
62.5
68
Heating connection
Ø
1" [F]
1" [F]
1" [F]
Domestic hot water connection
Ø
3/4
" [M]
3/4
" [M]
3/4
" [M]
DHW cylinder heat exchange surface
m
2
1.59
1.99
2.46
Heating circuit pressure drop
mbar
15
25
37
Flue gas circuit pressure drop
mbar
0.25
0.30
0.45
A
B
C
D
E
F
Ø G
H
I
J
K
L
Kg (*)
(mm)
(mm) (mm) (mm) (mm) (mm)
(mm) (mm) (mm) (mm) (mm) (mm)
Delta Pro 25
1760
540
584
1386
360
200
100
220
1445 1445
928
1400
145
Delta Pro 45
1760
540
584
1386
390
200
100
220
1445 1445
928
1400
168
Delta Pro 55
1760
540
584
1586
390
200
100
220
1645 1645
928
1600
200
(*) Empty weight without burner
BG 2000-S
Low NOx air/gas premix
burners are outstanding not only for
their eco-friendly design but also for
their incredibly silent operation. They
are fitted with automatic ignition and
an ionisation flame detector.
Floor standing combination
boiler. Offers exceptional heating
and hot water performance.
Available in Gas, Oil and Propane.
Benefits
The Delta Pro is reliable, economical and easy to use and maintain. It
is also oil, natural gas or propane compatible. The Delta Pro offers
versatility and convenience.
Product Features
• High performance low-cost combined boiler and water heater
• Stainless steel Tank-in-Tank design
• Choice of burner:
- Low-NOx premix burner
- Pressure jet natural gas or LPG
- Pressure jet 28 sec or 35 sec oil
• Anti-Legionellae: hot water stored at consistently high
temperature
• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
• Control panel including thermostats, thermometer, indicators and
on/off switch
• 26 to 55 kW output
• Can be used in battery formation for high output installations
• Vented or unvented use, with mains pressure SystemPaks
available
• Primary heating sealed system kits also available
1. Flue reduction collar with easy access
for servicing
2. Rigid polyurethane foam insulation
3. PVCC dip tube with cold water diffuser
4. Control thermostat and thermometer
bulb
5. Burner chamber plate with refractory
ceramic fibre insulation
6. 95 °C cut-off thermostat and manual
reset safety thermostat bulb
7. Flue tubes
8. Turbulators
9. Stainless steel "Tank-in-Tank" hot water
cylinder
10. Primary circuit (heating)
11. Combustion chamber
12. Boiler base
13. Heating flow
14. Heating return
15. Domestic hot water outlet
16. Domestic cold water supply
17. Expansion relief valve [6 bar]
18. Primary heating safety valve [3 bar]
19. Flue connection Ø 100 mm
20. Drain down valve
Delta Pro 25
Delta Pro 45
Delta Pro 55
Litres in first 10 minutes
40°C
268
316
362
Litres in first 10 minutes
45°C
202
275
348
Litres in first 10 minutes
60°C
117
161
209
Litres in first hour
40°C
806
1284
1533
Litres in first hour
45°C
672
911
1156
Litres in first hour
60°C
384
549
689
Continuous flow 40°C
Ltrs/hr
645
1161
1405
Continuous flow 45°C
Ltrs/hr
564
763
970
Continuous flow 60°C
Ltrs/hr
320
465
576
Initial heat up time 60°C
min
32
16
16
Tank reheat time at 60°C
Initial heating time
Minutes
32
16
16
After drawing off 140 litres at 45 °C
Minutes
15
9
7
Delta Pro 25/45/55