Installation and Commissioning Guide - Wall Hung Split System
Doc. No.9590-5007
Ver. 2 210416
Installation and Commissioning Guide
Wall Hung Split System
38
11.06. Electrical Connection
INTER-CONNECTING
POWER CABLE
OUTDOOR - INDOOR
MAIN
SUPPLY FROM
DISTRIBUTION
BOARD
SUB-MAIN
TO UNIT
OUTDOOR
UNIT
REMOTE
CONTROLLER
INTER-CONNECTING
PCB CABLE INDOOR
TO OUTDOOR
SUB-MAINS
ISOLATOR
(Field Supplied
by Installer)
SUB-MAINS
CIRCUIT
BREAKER
2
3
1
INDOOR
UNIT
MAINS WIRING (220-240VAC)
(Single Phase + Neutral) 50Hz
1.0 mm
2
- WRC-026CS / WRC-035CS
1.5 mm
2
- WRC-050CS
2.5 mm
2
- WRC-072CS
4.0 mm
2
- WRC-085CS
INTERCONNECT WIRING (220-240VAC)
(Single Phase + Neutral) 50Hz
1.0mm
2
- WRC-026CS / WRC-035CS
1.5mm
2
- WRC-050CS / WRC-072CS / WRC-085CS
3
2
1
EXTRA LOW VOLTAGE DATA CONTROL WIRING
2 core shielded data cable 14/0.20 (0.44mm
2
)
maximum 65 metres
EXTRA LOW VOLTAGE DATA CONTROL WIRING
4 core shielded data cable (0.75mm
2
)
maximum 12 metres
WALL
CONTROLLER
(Optional)
DATA CABLE
(Supplied with the
controller-6metres)
4
4
120mm
or more
2300mm or more
120mm
or more
Distance from ceiling is determinded
by the installation method.
Humidity
Boost