Installation and Commissioning Guide
Wall Hung Split System
Installation and Commissioning Guide - Wall Hung Split System
Doc. No.9590-5007
Ver. 2 210416
31
Follow these instructions to prevent distortion when the compressor starts:
• The unit must be connected to its individual sub-circuit. Ensure sub-circuit mains are of adequate size to ensure
minimal voltage drop at supply terminals.
• No other equipment should be connected to the same sub-circuit as the air conditioning unit.
• The unit’s power information can be found on the rating sticker on the product.
NOTE
The air conditioners circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the
fuse are printed on the circuit board, such as: T5A/250VAC, T10A/250VAC, etc.
Multi-Function Board
The installation of a multi-function board allows the connection of the following options:
•
Remote ON/OFF
•
Wired Controller (WC-02)
•
Alarm relay output
Remote On/off
To use, remote On/Off connect wiring and switch cross CN46 and remove jumper wire that is currently in the terminals.
Remote on/off will work by the following two options:
DIP switch F2: OFF/OFF
Current Running Operation
CN46
Operation
CP
Unit ON
Open
OFF
CP
Closed
No Change
No CP
Unit OFF
Open
No Change
CP
Closed
ON Last
Setting
No CP
DIP switch F2: ON/ON
Current Running Operation
CN46
Operation
CP
Unit ON
Open
OFF
No CP
Closed
No Change
No CP
Unit OFF
Open
No Change
No CP
Closed
ON Auto 24°C
No CP
CP – No Control Operation
No CP – Remote/Wired controller operation
N/O and N/C can be reversed by adjusting DIP switches. See wiring diagram for DIP switch settings.