![ActronAir PKV290T-L Installation And Commissioning Manual Download Page 46](http://html.mh-extra.com/html/actronair/pkv290t-l/pkv290t-l_installation-and-commissioning-manual_2844143046.webp)
PRELIMINARY DATA ONLY Ver. 5.01 210406
THIS LABEL TO BE REMOVED ON SIGN-OFF
46
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-067 Ver. 5 210414
Installation and Commissioning Guide
Variable Capacity Commercial
17.03. PKV290T-L/R
APPLICATION RANGE (COMPRESSOR ON)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
1200
34
327
38
417
42
519
46
631
50
741
55
884
1250
36
350
41
470
44
551
48
658
53
799
57
914
1300
39
398
43
499
47
603
51
710
55
823
59
959
1350
41
423
45
526
49
627
54
763
58
892
62
1004
1400
43
449
48
574
52
679
56
793
60
922
64
1039
1450
46
498
51
622
55
728
59
856
63
983
67
1102
1500
49
543
54
671
58
792
62
915
66
1041
70
1178
1550
52
589
56
697
60
821
65
970
69
1106
73
1221
1600
55
635
59
756
63
874
67
1000
71
1136
76
1290
1650
58
693
62
810
66
930
70
1063
75
1231
78
1317
1700
61
745
65
860
70
1020
74
1152
78
1293
84
1438
1750
64
795
68
916
73
1076
77
1211
81
1348
88
1505
1800
67
847
72
1003
76
1133
81
1305
85
1454
93
1582
REDUCED AIRFLOW (COMPRESSOR OFF)
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
350
21
266
400
20
280
23
297
450
22
315
24
366
500
MOTOR / BLOWER LIMIT
21
273
23
320
26
390
550
22
281
25
348
28
431
600
21
244
24
308
27
383
29
437
650
22
252
25
314
28
389
31
466
700
20
198
24
279
27
347
30
419
33
501
750
22
225
26
307
29
377
32
452
35
532
800
23
230
27
313
31
407
34
484
37
565
850
20
164
25
254
29
342
33
438
36
516
39
598
900
22
188
26
261
31
370
35
469
38
548
42
655
950
24
209
28
287
32
375
36
473
40
579
44
699
1000
26
232
30
311
34
403
38
505
42
615
46
724
1050
28
256
32
340
36
431
40
533
44
650
48
766
1100
30
279
34
366
38
460
42
567
46
683
51
823
1150
32
304
36
391
40
486
44
600
48
714
53
853
NOTES:
*
Reduced fan airflow is the airflow during compressor OFF operation (optional feature)
W
= Indoor Fan Power, Watts
PWM
= Pulse Width Modulation Setting, % PWM (Adjustable through NEO / LC7-2 Control Interface or Outdoor Board)
Default Fan Speed Value
Speed
Default PWM
Indoor Fan PWM Limits
High PWM (%)
70 (adjustable)
High PWM (%)
99
Medium PWM (%)
52 (adjustable)
Low PWM (%)
33
Low PWM (%)
38 (adjustable)