Installation and Commissioning Guide
Variable Capacity Commercial
23
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-076 Ver. 3 210414
13.03. Wiring Configuration 2 : Alternate
1
3
LM-RS-2
(OPTIONAL)
AERSS
(OPTIONAL)
LC7-2
WALL CONTROL 3
(OPTIONAL)
2a
2b
2c
LC7-2
WALL CONTROL 2
(OPTIONAL)
LC7-2
WALL CONTROL 1
(OPTIONAL)
NOTES
• Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
ITEM
DESCRIPTION
MAXIMUM CABLE LENGTH
1 to 2a
Indoor PCB to Wall Control 1 (optional)
100 m
1 to 2c
Indoor PCB to Wall Control 3 (optional)
75m total (Daisy Chain)
*
1 to 3
Indoor PCB to Remote Sensor
100 m
*
Maximum Daisy Chain connection is up to 2 Wall Control.
DESCRIPTION
CABLE TYPE
LC7-2 Field Control Wiring
Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5E UTP (AWG24) Data Cable