37
Installation and Commissioning Guide
Split Ducted ESP Indoor Unit
Installation and Commissioning Guide - Split Ducted ESP Plus/Ultima Indoor Unit
Doc. No.0525-078
Ver. 2 190925
Fan Mode
"
FAn
" will be displayed on Zone Control display when the master Wall Control is set to fan only. During this period,
the zone damper will be in the fully open position for maximum air circulation. Use this mode when air balancing the
system on commissioning or for (indoor) fan only ventilation.
ROOM
TEMP
MODE
ON/OFF
SET
ZONE
ESP AUTO
TEMP
Z O N E
C O N T R O L
1. Press the
button to turn Off the zone damper.
Display Room Temperature
Normally the Zone Control will show the setpoint temperature of the zones. To check the actual temperature of the
zone, see below:
1. Press the
button to display the actual Room/Zone temperature for 5 seconds. During this time the room temp
LED flashes. Room temperature display is accessible in all Zone Control operating modes
NOTE
To display room temperature for 45 minutes, press and hold
the
button for 5 seconds.
Room temperature LED will flash indicating the room temperature is shown on the display.
To Check Temperature at Master Wall Control
Average Room Temperature Display
1. Press the
or
buttons and the average room temperature will be displayed for 3 seconds.
INSIDE
,
o
C
and
.
indicators will be flashing. The temperature displayed is the average of all activated zone sensors.