
21
Installation and Commissioning Guide
Split Ducted ESP Indoor Unit
Installation and Commissioning Guide - Split Ducted ESP Plus/Ultima Indoor Unit
Doc. No.0525-078
Ver. 2 190925
10.02. Zone Control (LM-ZC-2 for ESP Ultima only)
Install Zone Control at approximately 1.5m above the floor.
Use the provided mounting template to ensure correct alignment and leveling of the Zone Control to the wall (Refer to
Page 29 for mounting details).
IMPORTANT NOTE
Do not locate Zone Control
on external walls, directly below the supply air grille or near other additional heat load sources, as
these locations may alter sensor readings.
1. Remove cover plate as shown below
• Use small flat blade screwdriver to fit into the slot in order to
avoid damaging the Zone Control.
• Insert and gently twist screwdriver into the slot at the side
of the controller. Do this procedure alternately between the
two slots until the front of the control separates from the
back cover.
SCREWDRIVER
SLOT
SLOT
COVER
PLATE
CONTROLLER
BASE
2. Detach the cover plate carefully from Zone Control base as
shown below
COVER
PLATE
ROOM
TEMP
MODE
ON/OFF
SET
TEMP
Z O N E
C O N T R O L
SCREW
HOLES
CONTROLLER
BASE
TEMPERATURE
SENSOR