UNIT DIMENSIONS / CLEARANCES CRQ2-14AS
OVERALL NOMINAL DIMENSION (H x W x L)
= 990 x 1320 x 580
USE M12 BOLT FOR FEET MOUNTING
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES, CONDENSER
AIR MUST NOT RECIRCULATE BACK ONTO CONDENSER COIL.
KEEP ALL CLEARANCES FREE OF ANY OBSTRUCTIONS
600 mm
SERVICE
CLEARANCE
(COMPRESSOR
AND
ELECTRICALS)
COMP.
HEIGHT CLEARANCE = 1500
A
B
C
D
OUTDOOR COIL
300 mm
SERVICE / AIRFLOW CLEARANCE
300 mm
SER
VICE /
AIRFLOW
CLEARANCE
NIL - TO - MINIMUM SERVICE CLEARANCE
UNIT MODEL
NUMBER
UNIT
WEIGHT
(kg)
CORNER WEIGHTS
(kg)
A
B
C
D
CRQ2-14AS
139
22.1
47.3
23.1
46.5
STANDARD PLATINUM MODEL
C
TOP VIEW
SIDE VIEW
FRONT VIEW
550
65
990
O/A
870
110 115
57.5
115 110
57.5
985
(MTG C-C DIST)
1320 O/A
255
565
255
580
O/A
COMP
OUTDOOR COIL
OUTDOOR
AIR INLET
OUTDOOR
AIR INLET
DRAIN
POINT
OUTDOOR
AIR OUTLET
OUTDOOR
AIR INLET
925
35
30
25
25
517
(MTG C-C DIST)
NOTES:
1.
Do not scale drawing. All dimensions are in mm unless specified. Refer
to corresponding unit dimensional drawing for mounting hole details.
2.
Service Access Areas and Spaces for Airflow Clearances given above
are suggested minimum based on the condition that the spaces around
the units are free from any obstructions and a walkway passage of
1000mm between the units or between the unit and the outside perimeter
is available.
3.
Minimum service access areas and spaces for airflow clearances are
responsibilities of the installer, ActronAir will not be held liable for any
extra charges incurred due to lack of access and space for airflow.
4. Under all circumstances, condenser air must not recirculate back onto
condenser coil. Keep all clearance free of any obstructions.
5.
Maximum External Static of Outdoor Fans is 5 Pa.
6.
STACKING OF UNITS: Ensure that minimum airflow and clearances are
met.
7.
Refer to Pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9.
Use M12 bolt for feet mounting.
THIRD ANGLE