WIRING DIAGRAM MATRIX - SPLIT DUCTED MODELS
MODEL
WIRING DIAGRAM
CRQ2-14AS / ERQ2-14AS
WD2010
CRQ3-17AS / ERQ3-17AS
CRQ4-19AS / ERQ4-19AS
CIRCUIT BREAKER SIZE AND CABLE SIZE REQUIREMENT
MODEL
Circuit
Breaker Size
Cable Size
*
(mm)
Amps
MAIN
O.D. to I.D.
CRQ2-14AS / ERQ2-14AS
25.0
4.0
1.0
CRQ3-17AS / ERQ3-17AS
32.0
6.0
1.0
CRQ4-19AS / ERQ4-19AS
32.0
6.0
1.0
* Suggested Minimum Cable Size should be used as a guide only, refer to AS/NZS
3000 “Australian / New Zealand Wiring Rules” for more details.
ELECTRICAL INSTALLATION