Installation and Commissioning Guide
ICUNO-MOD
11
10
Installation and Commissioning Guide ICUNO-MOD
Doc. No. 9590-3013
Ver. 5 200722
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
04.05.02. Configure Baud Rate and Data Parity
SW2-BMS SETTINGS DIP SWITCH
Modbus RS-485 Baud Rate and Data Parity can be configured by setting SW2 as per the table below.
Function
SW2 - DIP Switch
1
2
3
4
Data
Parity
NONE
ON
EVEN
OFF
Baud
Rate
9600
OFF
OFF
OFF
19200
OFF
OFF
ON
38400
OFF
ON
OFF
57600
OFF
ON
ON
76800
ON
OFF
OFF
115200
ON
OFF
ON
NOTE:
The Data Parity and Baud Rate must be the same for all the devices connected on the local RS-485 network, otherwise
the exchange of data will generate communication errors. If the BMS card has the incorrect data parity or baud rate,
then the Status 2 LED (white) will FLASH slowly (once every 2 seconds). See Section 04.07 for BMS Troubleshooting.