Installation and Commissioning Guide
ICUNO-MOD
23
22
Installation and Commissioning Guide ICUNO-MOD
Doc. No. 9590-3013
Ver. 5 200722
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
Description
Digital / In
ver
ter
C
lassic II
Ty
p
e
M
o
dbus
R
egist
er
R
ead
/W
rit
e
UoM
M
in
M
ax
C
ompr
ess
or 1 S
tatus
Compressor 1 running status
(0=Off, 1=On)
l
l
Analog
1101
R
1
0
1
Compressor 1 Heating (0=Off, 1=On)
l
l
Analog
1102
R
1
0
1
Compressor 1 Demand (0.1%)
l
l
Analog
1104
R
0.1%
0.0%
100.0%
Compressor 1 Speed (0.1%)
l
Analog
1105
R
0.1%
0.0%
100.0%
Compressor 1 Unit Defrosting
(0 = Off, 1 = Defrosting)
l
l
Analog
1107
R
1
0
1
Compressor 1 Suction Pressure (kPa)
l
Analog
1111
R
1kPa
0kPa
6000kPa
Compressor 1 Discharge Pressure (kPa)
l
Analog
1112
R
1kPa
0kPa
6000kPa
Compressor 1 Suction Temperature (0.1°C)
l
Analog
1113
R
0.1°C
-999.9°C
999.9°C
Compressor 1 Discharge Temperature
(0.1°C)
l
Analog
1114
R
0.1°C
-999.9°C
999.9°C
Compressor 1 Suction Superheat (0.1°K)
l
Analog
1115
R
0.1°K
-99.9°K
99.9°K
Compressor 1 Suction Superheat Target
(0.1°K)
l
Analog
1117
R
0.1°K
-99.9°K
99.9°K
Compressor 1 LP Switch Trip (0=Off, 1=Trip)
l
l
Analog
1118
R
1
0
1
Compressor 1 HP Switch Trip (0=Off, 1=Trip)
l
l
Analog
1119
R
1
0
1
Compressor 1 HP or LP Lockout
(0=Off, 1=Lockout)
l
l
Analog
1122
R
1
0
1
OD C
oil
Outdoor Coil 1 Temperature (0.1°C)
l
l
Analog
1201
R
0.1°C
-99.9°C
99.9°C
Outdoor Coil 1 Fan Speed Setting
(0=Off, 1=Low, 2=Med, 3=High)
l
l
Analog
1215
R
1
0
3
ID C
oil
Indoor Coil Temperature (0.1°C)
l
l
Analog
1301
R
0.1°C
-99.9°C
99.9°C
Indoor Coil 1 Fan 1 Speed (0.1%)
l
l
Analog
1311
R
0.1%
0.0%
100.0%
Indoor Coil 1 Fan 1 Speed (RPM)
l
l
Analog
1312
R
1RPM
0RPM
9999RPM
EEV
Compressor 1 EEV position (0.1%)
l
Analog
1401
R
0.1%
0.0%
100.0%
Compressor 1 Discharge Temp High
(0=Off, 1=On)
l
Analog
1502
R
1
0
1
Compressor 1 LP Status
(0 = OK, 1 = Error)
l
Analog
1503
R
1
0
1
Compressor 1 HP Status
(0 = OK, 1 = Error)
l
Analog
1504
R
1
0
1
Compressor 1 Suction Temperature Status
(0 = OK, 1 = Error)
l
Analog
1505
R
1
0
1
Compressor 1 Discharge Temperature
Status (0 = OK, 1 = Error)
l
Analog
1506
R
1
0
1
Outdoor Coil 1 Temperature Status
(0 = OK, 1 = Error)
l
l
Analog
1507
R
1
0
1
Indoor Coil Temperature Status
(0 = OK, 1 = Error)
l
l
Analog
1508
R
1
0
1