background image

Actionair DWFX-F Installation Guide

4

Swegon reserves the right to alter specifications.       20210408 - LNNN00354 (3.0)                                                                   

Vertical Damper, Alblative Batt in a 

Plasterboard Wall

Actionair SmokeShield PTC - [AA/F10710]
Actionair FireShield - [AA/F10711]

Installation Method

1. Mark out the hole on the partition and cut it out, cut-

ting the top and bottom edges first to maintain stabi

-

lity.

2. Frame out the hole with stud and track and cover this 

with 2 layers of board. Finish edges with joint filler.

3. 

Rivet steel duct (by others) to damper spigot on non-

access side, using steel rivets.

4. Suspend the damper from the ceiling, using 10mm 

studding drop rods, and support the damper from 

lateral movement.

5. Make sure the area within the aperture and the 

damper casing is free from any debris and remove any 

dust.

6. Where the coated BATT will contact the surrounding 

aperture apply Rockwool Fire pro glue to the outer 

edges of the BATT.  Where two coated BATTS are in 

contact use Rockwool fire pro glue as the joint adhe

-

sive. In both cases ensure that an even cover is achie-

ved over the entire thickness of the BATT.

7.  Continue installation of Rockwool ablative coated 

BATT, until aperture is completely filled.

8. 

Apply a bead of Rockwool acoustic intumescent sealant 









Comments:

Rev:

Drawn By:

S.Wehrle

Approved By:

N.Harris

1  of 1 

Reference No:

S.Gore

Date:
Date:

By:

Date:

13/04/18

15/07/10

13/04/18

Date:

G

Checked By:

Sheet

Rev

AAF10710

Description:

If  your proposed installation details

differ from that shown here, please

discuss this with the Building Control Authority

(BCA), referencing this documentation, 

associated fire tests, assessments, and other 

documentation shown below. Deviation from 

this drawing requires the approval of the 

relevant authority.

Installation Detail

Connecting ductwork omitted for clarity.  

Ductwork must be independently supported.  

There must be an appropriate break-away 

joint between the damper and connecting 

ductwork on both sides of assembly.  

Aluminium rivets or plastic cleats, clips, 

clamps and bolts etc.  should be used for this, 

unless fire resisting ductwork is being used 

where fire resisting fixings should be used.  A 

minimum of 200 mm between fire dampers 

installed in separate ducts and 75 mm 

between fire damper and a construction 

element (wall/floor).





















³



















































































































































































IF YOUR PROPOSED

INSTALLATION DETAIL DIFFERS

FROM THAT SHOWN, YOU MUST

DISCUSS THIS WITH THE

BUILDING CONTROL AUTHORITY

(BCA), REFERENCING THIS

DOCUMENT AND THE

ASSOCIATED FIRE TESTS,

ASSESSMENTS AND OTHER

DOCUMENTS SHOWN BELOW.

DEVIATION FROM THIS DRAWING

REQUIRES THE APPROVAL OF

THE RELEVANT AUTHORITY.















































 

 

 

 

© Swegon Air Management Limited

South Street, Whitstable, Kent CT5 3DU

 

Tel:  +44 (0)1227 276100

Fax: +44 (0)1227 264262

 

www.swegonair.co.uk

Applicable Test Report to 

BS EN1366-2: 

BRE 267924

MINUTES

ES 120

Fire Resistance

Integrity and Leakage

E

EC1770

MJB 20-02-18

Damper Size Range (mm)

VERTICAL APPLICATION

SMOKE  DWFX-F &

ABLATIVE BATT

200 x 200 to 1000 x 1000

VERTICAL BLADES;

DAMPER CAN BE INSTALLED WITH THE

  BLADES IN THE VERTICAL ORIENTATION

  WITH THE ACTUATOR MOUNTED AT

  EITHER  THE TOP OR BOTTOM.  







 







 















F

EC1830

RTC 20/03/18

G

EC1839

RTC 13/04/18

to both sides of the wall, approximately 15mm wide, 

around the perimeter of the aperture between dry wall 

and BATT, ensuring that any gaps between the BATT 

and surrounding edges are fully filled.

9. 

Allow 12 hours for BATT penetration seal to cure prior 

to removing any lateral damper supports.

10. Alternative partition systems to those shown within 

this installation manual can be used if they have been 

shown by test to have at least the same fire resistance 

when tested to BS EN 1364-1:1999 as is required  of 

the damper. If the partition system has been success-

fully tested without stone mineral wool it does not 

have to be used in practice when only considering the 

fire performance of the complete system. The mineral 

wool may still be needed for other reasons e.g. acous-

tic performance.

11.  Connecting ductwork omitted for clarity. Ductwork 

must be independently supported. There must be an 

appropriate break-away joint between the damper and 

connecting ductwork on both sides of assembly. Alu-

minium rivets or plastic cleats, clips, clamps and bolts 

etc. should be used for this, unless fire resisting duct-

work is being used where fire resisting fixings should 

be used. A minimum of 200 mm between fire dampers 

installed in separate ducts and 75 mm between fire 

damper and a construction element (wall/floor).

12. For SmokeShield installations, please reference the 

actuator installation information on page 11.

Summary of Contents for DWFX-3F

Page 1: ... are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs between the blades Larger dampers must be handled in accordance with current regula tions and good practice due to weight Drawings Please visit our website to download the installation dra wings which are located on the rel...

Page 2: ...f a multiple damper assembly or if a non standard install is requi red talk to us as early as possible in the project to get important stakeholders engaged and ensure an instal lation solution can be found The instructions are based on the tested method using Actionair Smoke Shield PTC fire smoke dampers and Firetherm products Our SmokeShield dampers are designed to be used with fire separating el...

Page 3: ...g ductwork omitte Ductwork must be independ There must be an appropria between the damper and co on both sides of assembly A plastic cleats clips clamps should be used for this unle ductwork is being used whe fixings should be used A m between fire dampers instal ducts and 75mm between fi construction element wall fl Applicable Test R BS EN1366 P112628 1 BRE 2564 MINU ES 120 Fire Resistance and Le...

Page 4: ...d be us unless fire resisting ductwork is bei where fire resisting fixings should b minimum of 200 mm between fire d installed in separate ducts and 75 m between fire damper and a constru element wall floor Swegon Air Management L South Street Whitstable Kent C Tel 44 0 1227 276100 Fax 44 0 1227 264262 www swegonair co uk Applicable Test Report BS EN1366 2 BRE 267924 MINUTES ES 120 Fire Resistance...

Page 5: ...e resisting duct work is being used where fire resisting fixings should be used A minimum separation of 200 mm between fire dampers installed in separate ducts and 75mm bet ween fire damper and a construction element ie wall floor unless otherwise tested 12 Alternative partition systems to those shown within this installation manual can be used if they have been shown by test to have at least the ...

Page 6: ...ved By N Harris 1 o Reference No S Gore Checked By She AAF10706 Description If your proposed installation de differ from that shown here ple discuss this with the Building C BCA referencing this docume associated fire tests assessme documentation shown below D this drawing requires the appro relevant authority Installation D Connecting ductwork omitted fo Ductwork must be independent There must be...

Page 7: ...cumenta below Deviation from this drawing r the approval of the relevant authorit Installation De Connecting ductwork omitted for cla Ductwork must be independently su There must be an appropriate break between the damper and connecting on both sides of assembly Alumini plastic cleats clips clamps and bolt should be used for this unless fire r ductwork is being used where fire re fixings should be...

Page 8: ...tion information on page 11 Comments Rev Drawn By M Bushell Approved By S Wehrle 1 of 1 Reference No S Gore Date Date By 2 2 2 Date Checked By Sheet AAF12493 Description If your proposed installation details d that shown here please discuss this Building Control Authority BCA refe this documentation associated fire te assessments and other documentati below Deviation from this drawing re the appro...

Page 9: ...ng ductwork is where fire resisting fixings shou minimum of 200 mm constructio wall between fire dampers inst separate ducts and 75 mm betw damper and a construction elem A A B B C C D D Swegon Air Managemen South Street Whitstable Ken Tel 44 0 1227 276 Fax 44 0 1227 264 www swegonair co Applicable Test Rep BS EN1366 2 WF388114 MINUTE ES120 Fire Resistance Int and Leakage VERTICAL BLADES The dampe...

Page 10: ...rehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 9999 2017 Code...

Page 11: ...tion Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner des...

Page 12: ...MPER MADE BETWEEN 4 6 M FULLY OPEN AC DC 230V 50 60 Hz 14 VA 12 4 W 30 C 50 C CONTINUOUS TF 72 C AC 250V 6 3 A N CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN Supply Off Damper s...

Page 13: ...GHT DUCT DIA 245mm FOR DUCT DIAMETERS BET EEN 970mm 1000mm OVERALL WIDTH OF FLAN E WIDTH IS 1198mm OVERALL HEIGHT OF INSTALLATION FRAME IS 1195mm OVERALL FLANGE WIDTH DUCT DIA 248mm OVERALL FLANGE HEIGHT DUCT DIA 245mm FOR DUCT WIDTHS BETWEEN 970mm 1000mm OVERALL WIDTH OF INSTALLATION FRAME IS 1198mm Flat Oval Dampers Series 701 C Circular Dampers Series 601 FOR DAMPERS 100 150MM 2 FOR IRCULAR DAM...

Page 14: ...ts OVERALL FLANGE WIDTH DUCT WIDTH 198mm OVERALL FLANGE HEIGHT DUCT HEIGHT 195mm For Ducts with widths and heights of 200 1000mm FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM OVERALL FLANGE WIDTH IS 398mm UCT WIDTHS A OVERALL FLANGE HEIGHT IS 395mm FOR D ND HEIGHTS OF 100 150MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM OVERALL FLANGE WIDTH IS 448mm OVERALL FLANGE HEIGHT IS 445mm FOR OVERAL...

Page 15: ...DWFX F Installation Dimensional Data Base Dampers Dampers with DWFX F Series 101 FireShield Dampers with blades partly in airstream Damper spigots stream Series 201 spigots 5mm under duct size 100 249 high use Series 101 Damper as Series 301 spigots 3mm under duct size Series 401 spigots 3mm under duct size Actionair FireShield ...

Page 16: ...nning vertically 6 Is access through the ductwork to the damper unob structed Unobstructed space should be provided for safe access to the damper This must include access through ceiling voids and ad jacent services Damper installer to advise the system designer if problems are foreseen 7 Has the space around the damper and within the opening been left clear and not been used for other services Ot...

Reviews:

Related manuals for DWFX-3F