Actionair DWFX-F Installation Guide
12
Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
DWFX-F Wiring Diagrams
Close Time ≈ 22 secs.
Open Time ≈ 60 secs.
(Connect 24V via a safety isolating
transformer.)
IP54 Rated.
Supply On – Damper motors open.
Electrical Thermal Release.
External mechanical position indicator
with pointer.
WHITE (2)
BLACK (1)
1
2
3
4
5
6
_
+
COMMON
SUPPLY 24V AC or DC
TYPICALLY 10W (MOTORING
2W (RESET)
CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED
COMMON
VOLT FREE CONTACT
MADE BETWEEN 1 & 2
WHEN DAMPER
FULLY CLOSED
M
AC/DC 24V
50 / 60 Hz
12.5 VA
VOLT FREE CONTACT
MADE BETWEEN 4 & 6
WHEN DAMPER
FULLY OPEN
10 / 2 W
Imax
8.3A @ 5ms
-30°C...+50°C
CONTINUOUS
TF 72°C
AC
250V
6(3)A
ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).
(SPRING BIASED TEST SWITCH)
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
Supply Off – Damper spring closes.
Mode 6 PTC 230V
Supply On – Damper motors open.
Electrical Thermal Release.
External mechanical position indicator
with pointer.
Close Time ≈ 22 secs.
Open Time ≈ 60 secs.
(To isolate from main power supply, the
system must incorporate a device which
disconnects the phase conductors, with at
least 3mm contact gap.)
Note: 120V A.C. version also available.
IP54 Rated.
BLUE
BROWN
1
2
3
4
5
6
L1
COMMON
COMMON
SUPPLY 230V AC 50/60Hz
TYPICALLY 12W (MOTORING
4W (RESET)
VOLT FREE CONTACT
MADE BETWEEN 1 & 2
WHEN DAMPER
FULLY CLOSED
VOLT FREE CONTACT
WHEN DAMPER
MADE BETWEEN 4 & 6
M
FULLY OPEN
AC/DC 230V
50 / 60 Hz
14 VA
12 / 4 W
-30°C...+50°C
CONTINUOUS
TF 72°C
AC
250V
6(3)A
N
CONTINUITY WITH 'COMMON'
ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).
(SPRING BIASED TEST SWITCH)
WHEN DAMPER CLOSED
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
Supply Off - Damper spring closes.
Mode 5-3P
Supply On – Damper motors open.
Spring close time ≈ 18 seconds
Motor open time ≈ 120 seconds
(Connect 24V via a safety isolating transformer.)
IP54 Rated.
The M5-3P is controlled by standard 0...10V
control signal. The actuator motors to the position
activated, power supply lost or removed the device
springs the damper to the fail-safe position.
Electrical thermal release (ETR)
_
+
~
T
1
2
3
4
5
6
COMMON
COMMON
VOLT FREE CONTACT
WHEN DAMPER
MADE BETWEEN 1 & 2
FULLY RELEASED
VOLT FREE CONTACT
MADE BETWEEN 4 & 6
WHEN DAMPER
FULLY RESET
TF 72°C
AC
250V
6(3)A
CONTINUITY WITH 'COMMON'
ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).
(SPRING BIASED TEST SWITCH)
WHEN DAMPER CLOSED
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED
CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN
WHITE (5)
WHITE (3)
Y DC 0...10V
U DC 2...10V
AC/DC 24V
50 / 60 Hz
9.5 VA
7 / 2.5 W
Imax
8.3A @ 5ms
M
-30°C...+50°C
CONTINUOUS
RED (2)
BLACK (1)
SUPPLY 24V A.C. or D.C.
TYPICALLY 6W (MOTORIN G
2W (HOLDING)
DIAGRAMS SHOWS ACTUATOR IN FULLY CLOSED STATE
NOTE THAT THE FOR INTERMEDIATE
POSITIONS, NEITHER OF THE
CONDITIONS BELOW WILL BE TRUE.
Supply Off - Damper spring closes.
specified by the control signal. If the ETR is
(Must be fitted to ducting for damper operation).
Mode 5 PTC 24V