0
Electrical Data - Cooling Only (R407C)
ACC 75D
ACC 100D
A4MC 75D
A4MC 100D
POWER SOURCE
V/Ph/Hz
RATED INPUT POWER
W
1061
1254
RATED RUNNING CURRENT
A
4.51
5.79
MOTOR OUTPUT
W
750
1000
4
4
POWER SOURCE
V/Ph/Hz
RATED INPUT POWER
W
RATED RUNNING CURRENT
A
MOTOR OUTPUT
W
N/A
N/A
POWER SOURCE
V/Ph/Hz
380 - 415 / 3 / 50
380 - 415 / 3 / 50
CAPACITOR
μ
F
NIL
NIL
RATED INPUT POWER
W
6045
9186
RATED RUNNING CURRENT
A
11.1
15.9
LOCKED ROTOR AMP.
A
95
125
ACC 75DR
ACC 100DR
A4MC 75ER
A4MC 100ER
POWER SOURCE
V/Ph/Hz
RATED INPUT POWER
W
1061
1254
RATED RUNNING CURRENT
A
4.51
5.79
MOTOR OUTPUT
W
750
1000
4
4
POWER SOURCE
V/Ph/Hz
RATED INPUT POWER
W
RATED RUNNING CURRENT
A
MOTOR OUTPUT
W
N/A
N/A
POWER SOURCE
V/Ph/Hz
380 - 415 / 3 / 50
380 - 415 / 3 / 50
CAPACITOR
μ
F
NIL
NIL
RATED INPUT POWER (COOLING)
W
6045
9186
RATED INPUT POWER (HEATING)
W
6045
7425
RATED RUNNING CURRENT (COOLING)
A
11.1
15.9
RATED RUNNING CURRENT (HEATING)
A
11.1
16.5
LOCKED ROTOR AMP.
A
95
125
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.
6
INSULATION GRADE
INSULATION GRADE
POLES
COMPRESSOR
INDOOR MOTOR
INSULATION GRADE
OUTDOOR MOTOR
POLES
MODEL
INDOOR UNIT
350
600
1.2
CLASS B
220 - 240 / 1 / 50
OUTDOOR UNIT
380 - 415 / 3 / 50
CLASS F
COMPRESSOR
INDOOR MOTOR
CLASS F
CLASS B
220 - 240 / 1 / 50
POLES
350
600
6
1.2
OUTDOOR MOTOR
INDOOR UNIT
OUTDOOR UNIT
INSULATION GRADE
MODEL
380 - 415 / 3 / 50
INSULATION GRADE
POLES
INSULATION GRADE
Summary of Contents for A4MC 100ER
Page 1: ...Ceiling Concealed D Series ACC D2 2007 ACC 75 D DR ACC100 D DR Models ...
Page 50: ...48 Model AMC A4MC 75 100D ER Note All Dimension are in mm Outdoor Unit ...
Page 53: ...51 Model ACC 75 100D vs AMC A4MC 75 100D Cooling Only 10 WIRING DIAGRAMS ...
Page 54: ...52 Heat Pump Model ACC 75 100DR vs Model AMC A4MC 75 100ER ...