Outdoor DB, ˚C
40
TC (kW)
SC (kW)
X
y
.7
.0
.0
.
Details:
1st Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition:
°C DB,
°C WB
Outdoor Condition:
°C DB
Indoor DB
Indoor WB
˚C
˚C
15
24
16
17
Total capacity, TC
=> X
1
= .0kW (Same as Total capacity at 0°C Indoor DB / °C Indoor WB & °C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
17˚C - 15˚C
14.560kW - y
17˚C - 16˚C
14.560kW - 15.069kW
=> y
= .7kW
(b) Indoor Condition:
°C DB,
°C WB
Outdoor Condition:
0°C DB
=
Indoor DB
Indoor WB
˚C
˚C
15
24
16
17
Total capacity, TC
=> X
= .kW
(Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
17˚C - 15˚C
13.523kW
- y
17˚C - 16˚C
13.523
kW - .0kW
=> y
= .7kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
=>
=>
=
Outdoor DB, ˚C
35
TC (kW)
SC (kW)
X
y
0.7
.0
0.70
.0