1-6
Please ensure that the following steps are taken:
• Unit installation should be
fi
lted at least 10mm as recommended in Figure B.
• The drain pipe slope shall be kept at least 1:100.
• Provide clearance for easy servicing and optimal air
fl
ow as shown in Figure C.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
400mm or more
250mm or more
1m or more
Floor Standing Type
250mm or more
Dimension
A
B
C
D
E
F
G
H
5CEY15/20/25E/ER
5CEY28ER
1073
534
268
135
336
630
145
485
Utensils, furnitures or built-in
architectural features must not
protrude more than 250 mm
Drainage Pipe
250mm or less
300mm
(Min.)
500mm or more
10mm
Indoor Unit
Hanger Bracket
Nut
Washer
Washer
Nut
Floor
2300mm or more
Ceiling
Figure C