Issue: O-WCP15-SEP21-2
Page 51
PERIODIC MAINTENANCE
–
YEARLY
Entire Unit Inspection
In addition to the checks listed in this section, periodic overall inspections of the unit should be accomplished to
ensure proper equipment operation. Items such as loose hardware, component operation, refrigerant leaks, unusual
noises, etc. should be investigated and corrected immediately.
Water Treatment
Water shall be treated in fortnightly basis,
i) To Prevent Scaling and Depositions
(Scale/deposits will decrease heat transfer and increase energy usage)
ii) To Inhibit Corrosion
(Corrosion will shorten the life of the equipment)
iii) To Control Microbiological Growth
(Microbiological activity will cause system blockages and potential health hazards)
iv) To Disperse and Fluidize Suspend Matters
(Suspended matters will cause system blockages, decrease heat transfer and increase energy usage)
v) To Control Legionnaire’s Pneumophila.
(Legionnaire’s disease will cause health hazards)
Table 10: Parameter for Condenser Water Treatment Control
Parameter
Limits
Action
pH
7.0
–
9.0 Bleed to reduce
TDS
<800 ppm as CaCo3 Bleed off to control
Total Alkalinity
<300 ppm as CaCo3 Bleed off to control
Chloride
<120 ppm as CL
Bleed off to control
Fe value
<2.5 ppm Add CWT 3753 to control
Total Hardness
<300 ppm as CaCo3 Bleed off to control
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
* R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new
refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation/servicing is essential.
* Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
* POE or PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22
compressor. During servicing, extra precaution must be taken not to expose the R410A system too long to moist air.
Residual POE or PVE oil in the piping and components can absorb moisture from the air.
* Use tools and materials exclusively for refrigerant R410A. Tools exclusively for R410A are manifold valve,
charging hose, pressure gauge, gas leak detector, flare tools, torque wrench, vacuum pump and refrigerant cylinder.
* If the refrigerant gas leakage occurs during installation/servicing, be sure to ventilate fully. If the refrigerant gas
comes into contact with fire, a poisonous gas may occur.
Summary of Contents for A5WCP0060A-FP
Page 13: ...Issue O WCP15 SEP21 2 Page 9 5 1 UNIT DIMENSION 5 1 1 Outline A5WCP0060A FP FS...
Page 14: ...Issue O WCP15 SEP21 2 Page 10 5 1 1 Outline A5WCP0090A FP FS...
Page 15: ...Issue O WCP15 SEP21 2 Page 11 5 1 3 Outline A5WCP0140A FP FS...
Page 16: ...Issue O WCP15 SEP21 2 Page 12 5 1 4 Outline A5WCP0180A FP FS...
Page 17: ...Issue O WCP15 SEP21 2 Page 13 5 1 5 Outline A5WCP0240A FS...
Page 18: ...Issue O WCP15 SEP21 2 Page 14 5 1 6 Outline A5WCP0280A FS...
Page 19: ...Issue O WCP15 SEP21 2 Page 15 5 1 7 Outline A5WCP0320A FS...
Page 20: ...Issue O WCP15 SEP21 2 Page 16 5 1 8 Outline A5WCP0360A FS...
Page 21: ...Issue O WCP15 SEP21 2 Page 17 5 1 9 Outline A5WCP0400 520A FS...
Page 22: ...Issue O WCP15 SEP21 2 Page 18 5 1 10 Outline A5WCP0570A FS...
Page 23: ...Issue O WCP15 SEP21 2 Page 19 5 1 11 Outline A5WCP0710A FS...
Page 24: ...Issue O WCP15 SEP21 2 Page 20 5 1 12 Outline A5WCP0870A FS...
Page 25: ...Issue O WCP15 SEP21 2 Page 21 5 1 13 Outline A5WCP0940A FS...
Page 29: ...Issue O WCP15 SEP21 2 Page 25 5 6 FAN CURVE 5 6 1 Fan Curve AT 9 9 Model A5WCP0060 A5WCP0090...
Page 30: ...Issue O WCP15 SEP21 2 Page 26 5 6 2 Fan Curve AT 15 15 Model A5WCP0140 A5WCP0180 A5WCP0240...
Page 31: ...Issue O WCP15 SEP21 2 Page 27 5 6 2 Fan Curve AT 18 18 Model A5WCP0280...
Page 32: ...Issue O WCP15 SEP21 2 Page 28 5 6 2 Fan Curve ADH 450 Model A5WCP0320 A5WCP0360 A5WCP0710...
Page 34: ...Issue O WCP15 SEP21 2 Page 30 5 6 2 Fan Curve ADH 560 Model A5WCP0570...