Issue: O-WCP15-SEP21-2
Page 48
INITIAL START-UP
After all the other preceding checks have been completed and the operator has familiarized himself with the
sequence of operation for the unit and all options provided, the unit can be put in operation. Proceed as follows:
1. Energize cooling tower water pump and tower fans. Set the water flow rate according to the design value.
2. Turn ON the MCB/MCCB (MCB single pole for control circuit, MCB three poles for power supply for three
phase motor) and press
button “START” on
the unit LCD wall pad.
3. If no abnormal noise or adverse conditions exist allow the unit to run. If these conditions does exist, turn off the
unit and investigate possible causes by taking below steps:
i) Check for correct power phasing to unit. Correct rotation on scroll compressor can be determined by a drop in
suction pressure and a rise in discharge pressure when the compressor is energized.
To reverse the rotation on a
three phase scroll compressor, simply swap connection of any two of the three compressor phases at the
power supply terminal and recheck operating pressures.
Running the compressor for a short period of time in
reverse direction will have no negative impact but prolonged running in reverse direction may cause premature
failure.
*A5WCP0060/090/140/180/320/360/400/520*-F*C* is supplied with external Supply Monitoring
Device factory preset: UV 90%, OV 5%, On Delay 1 Second, Off Delay 5 Second (Fixed).
* A5WCP0240/280/570/710/870/940*, the motor protection module comes preinstalled within the
compressor terminal box. The module had been terminated at control box of unit.
ii) Check for correct direction for air discharge (only apply to blower motor changed to opposite direction from
original position). Simply swap any two of the three wires at the power supply inlet to fan contactor terminal.
Incorrect wiring or blower rotation may trigger on the fan overload protector.
iii) Check for belt tensioning
4. Once the unit is run normal, take an air flow measurement in the straight duct off the unit discharge using a pitot
tube. This measurement should be taken about three quarters (3/4) of the way down the straight duct off the fan, just
before any transition or elbow. If a condition of low or high air flow exists, a pulley change may be required.
Once it is ascertained that the air quantity leaving the unit is according to the design CFM, the thermostats should be
set to the desired space temperature. The system should now function as designed.
Summary of Contents for A5WCP0060A-FP
Page 13: ...Issue O WCP15 SEP21 2 Page 9 5 1 UNIT DIMENSION 5 1 1 Outline A5WCP0060A FP FS...
Page 14: ...Issue O WCP15 SEP21 2 Page 10 5 1 1 Outline A5WCP0090A FP FS...
Page 15: ...Issue O WCP15 SEP21 2 Page 11 5 1 3 Outline A5WCP0140A FP FS...
Page 16: ...Issue O WCP15 SEP21 2 Page 12 5 1 4 Outline A5WCP0180A FP FS...
Page 17: ...Issue O WCP15 SEP21 2 Page 13 5 1 5 Outline A5WCP0240A FS...
Page 18: ...Issue O WCP15 SEP21 2 Page 14 5 1 6 Outline A5WCP0280A FS...
Page 19: ...Issue O WCP15 SEP21 2 Page 15 5 1 7 Outline A5WCP0320A FS...
Page 20: ...Issue O WCP15 SEP21 2 Page 16 5 1 8 Outline A5WCP0360A FS...
Page 21: ...Issue O WCP15 SEP21 2 Page 17 5 1 9 Outline A5WCP0400 520A FS...
Page 22: ...Issue O WCP15 SEP21 2 Page 18 5 1 10 Outline A5WCP0570A FS...
Page 23: ...Issue O WCP15 SEP21 2 Page 19 5 1 11 Outline A5WCP0710A FS...
Page 24: ...Issue O WCP15 SEP21 2 Page 20 5 1 12 Outline A5WCP0870A FS...
Page 25: ...Issue O WCP15 SEP21 2 Page 21 5 1 13 Outline A5WCP0940A FS...
Page 29: ...Issue O WCP15 SEP21 2 Page 25 5 6 FAN CURVE 5 6 1 Fan Curve AT 9 9 Model A5WCP0060 A5WCP0090...
Page 30: ...Issue O WCP15 SEP21 2 Page 26 5 6 2 Fan Curve AT 15 15 Model A5WCP0140 A5WCP0180 A5WCP0240...
Page 31: ...Issue O WCP15 SEP21 2 Page 27 5 6 2 Fan Curve AT 18 18 Model A5WCP0280...
Page 32: ...Issue O WCP15 SEP21 2 Page 28 5 6 2 Fan Curve ADH 450 Model A5WCP0320 A5WCP0360 A5WCP0710...
Page 34: ...Issue O WCP15 SEP21 2 Page 30 5 6 2 Fan Curve ADH 560 Model A5WCP0570...