2.2 Installation Guideline (Cable size)
Carefree Series Outdoor Units
Model
A5VR
030DRM
A5VR
035DRM
A5VR
040DRM
A5VR
050DRM
A5VR
050DRM(3)
A5VR
060DRM
A5VR
060DRM(3)
A5VR
065DRM
A5VR
070DRM
A5VR
080DRM
Power Supply
220V~/50Hz
380V/3N
~/50Hz
220V
~/50Hz
380V/3N
~/50Hz
220V
~/50Hz
380V/3N~/50Hz
Maximum Operating
Current (A)
23.9
24.3
24.6
34.3
16.1
34.3
16.1
34.3
18.7
18.7
Cable
Intersection
Surface(mm
2
)
4
4
4
6
4
6
4
6
4
4
Quantities
3
3
3
3
5
3
5
3
5
5
Note:
• The lead-in position of power cable must be provided a short circuit device with a sufficient capacity. This device has a contact separation of 3 mm at least.
• All cable shall be connected and fixed tightly, and connecting wires must be fixed on the line card.
• All wires must not touch the refrigerant pipes and compressors, motors and other moving parts, and all the conducting wires must undergo safety measures to
prevent water, dust, corrosion, vibration and rodents.
• All above intersection surface of power wires are minimum requirements. The actual specifications Influenced by radiation, temperature, length etc, please
adjust it according to the related electric manual.
Ceiling Concealed Indoor Units
Model
A5VCC
022V
A5VCC025V
A5VCC028V
A5VCC032V
A5VCC036V
A5VCC040V
A5VCC045V
A5VCC050V
A5VCC056V
A5VCC
063V
A5VCC
071V
Power Supply
220V~/50Hz
Cable
Intersection
Surface(mm
2
)
Normal
1.5
Electrical heater
1.5
2.5
Quantities
3
Model
A5VCC
080V
A5VCC
090V
A5VCC
100V
A5VCC
112V
A5VCC
125V
A5VCC
140V
A5VCC
160V
Power Supply
220V~/50Hz
Cable
Intersection
Surface(mm
2
)
Normal
1.5
Electrical heater
2.5
4
Quantities
3
Note:
• The lead-in position of power cable must be provided a short circuit device with a sufficient capacity. This device has a contact separation of 3 mm at least.
• All cable shall be connected and fixed tightly, and connecting wires must be fixed on the line card.
• All wires must not touch the refrigerant pipes and compressors, motors and other moving parts, and all the conducting wires must undergo safety measures to
prevent water, dust, corrosion, vibration and rodents.
• All above intersection surface of power wires are minimum requirements. The actual specifications Influenced by radiation, temperature, length etc, please
adjust it according to the related electric manual.