• Obstacles exist at upper side
a. Single unit installation (see Figure 13)
The relation of H, A, L is as follows:
L
A
L ≤ H
0 < L ≤ 1/2H
750
1/2H < L ≤ H
1000
H < L
The setting of foundation is L ≤ H
Seal the bottom of foundation to prevent the exhausted air from crossing the unit.
b. Group units installation (more than two units)(see Figure 14)
The relation of H, A, L is as follows:
L
A
L ≤ H
0 < L ≤ 1/2H
1000
1/2H < L ≤ H
1250
H < L
The setting of foundation is L ≤ H
Seal the bottom of foundation to prevent the exhausted air from crossing the unit,
Only install two units in the way.
Figure 13
Figure 14