44
890.0 mm (ceiling board opening)
790.0 mm (hanging rod)
890.0 mm (ceiling opening)
620.5 mm (hanging rod)
Piping
Direction
Unit size 820.0 mm
Unit size 820.0 mm
UNIT
Caution : Sharp edges and coil surfaces are potential injury hazard. Avoid from contact
with them.
PRELIMINARY SITE SURVEY
•
Electrical supply and installation is to conform to local authority's (e.g. National Electrical Board) codes and
regulations.
•
Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be independent of
welding transformer which can cause high supply fluctuations.
•
Ensure that the location is convenient for wiring, piping and drainage
•
The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and warm air
return, and must allow spreading of air throughout the room (near the center of the room)
•
Clearance must be provided for the indoor unit from the wall and obstacles as shown in the figure.
•
The installation place must be strong enough to support a load of 4 times the indoor unit weight to avoid amplifying
noise and vibration.
•
The installation place (handing ceiling surface) must be level and the height in the ceiling is 350 mm or more.
UNIT INSTALLATION
ACK-A
ACK-B
•
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
•
Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging
rod.
•
The installation template is extended according to temperature and humidity. Check on dimensions in using.
•
The dimensions of the installation template are same as those of the ceiling opening dimensions.
•
Before ceiling laminating work is completed, be sure to fit the installation template to the indoor unit.
Note: Be sure to discuss the ceiling drilling work with the installers concerned.
9. INSTALLATION OF INDOOR UNIT
Obstacles
Floor
Min 0.5 m
Min 0.5 m
Min 0.5 m
Max. 0.3 m
Beam
Ceiling board opening
Summary of Contents for A4LC 20B
Page 15: ...14 OUTDOOR UNIT ALC 30 40 50C CR A4LC 30 40 50 C CR...
Page 17: ...16 INDOOR UNIT COOLING ONLY MODEL ACK 30A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 18: ...17 INDOOR UNIT COOLING ONLY MODEL ACK 40 50A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50C...
Page 19: ...18 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 20: ...19 INDOOR UNIT HEAT PUMP MODEL ACK 30AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 21: ...20 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 23: ...22 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 24: ...23 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 26: ...25 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 27: ...26 INDOOR UNIT HEAT PUMP MODEL ACK 30AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 28: ...27 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 29: ...28 INDOOR UNIT COOLING ONLY MODEL ACK 15B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC15B...
Page 30: ...29 INDOOR UNIT COOLING ONLY MODEL ACK 20 25B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC20 25B...
Page 31: ...30 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC30C...
Page 32: ...31 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 33: ...32 INDOOR UNIT HEAT PUMP MODEL ACK 15BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 15BR...
Page 34: ...33 INDOOR UNIT HEAT PUMP MODEL ACK 20 25BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 20 25BR...
Page 35: ...34 INDOOR UNIT HEAT PUMP MODEL ACK 30BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30CR...