WIRELESS REMOTE CONTROL (UNIVERSAL BOARD)
Cooling : LED Indicator Light Display
Heatpump : LED Indicator Light Display
POWER
TIMER
SLEEP
HEAT
Operation / Faulty Indication
m
m
Timer on
m
m
Sleep mode on
m
m
Heat mode
¤
Continuously
m
/
l
Frost prevention mode
¤
Once every 3 sec
Compressor overload
¤¤
Twice every 3 sec
Pump fault
¤¤¤
3 Times every 3 sec
Gas leak
¤¤¤¤
4 Times every 3 sec
Room/indoor/outdoor coil sensor contact
loose/short
m
ON
m
/
l
ON OR OFF
¤
BLINKING
WIRED REMOTE CONTROL (UNIVERSAL BOARD)
Cooling / Heatpump Model
Error Code at 7 Segment Display
Operation / Faulty Indication
E1 Blinking
Room Sensor Contact Loose / Short
E2 Blinking
Indoor Coil Sensor Contact Loose / Short
E3 Blinking
Outdoor Coil Sensor Contact Loose / Short
E4 Blinking
Compressor Overload
E5 Blinking
Gas Leak
E6 Blinking
Pump Faulty
Heat LED Blinking
Outdoor Defrost ( For Heatpump Only)
Water Pump
The water pump will on if compressor is on during cooling cycle. The pump will remain on for at least 5 minutes after the
compressor is off.
During mode change from cooling to non-cooling mode, the pump will on for minimum 5 minutes. During defrost cycle,
the pump will on and will on for another 5 minutes once the defrost cycle is terminated.
Water level Switch
This normally close switch is to detect faults in water pump system. It will confirm for 30 seconds for switch open and 60
seconds for switch close.
Once switch is confirmed open, it will force compressor to cut off. If the switch is closed within 5 minutes, the compressor
is allowed to cut in. If the switch does not close for more than 5 minutes, the system will warn user regarding the fault,
the compressor is not allowed to cut in. If the switch is confirmed opened twice within 30 minutes, the system assumes
there are faults.
POWER
TIMER
SLEEP
POWER
TIMER
HEAT
Summary of Contents for A4LC 20B
Page 15: ...14 OUTDOOR UNIT ALC 30 40 50C CR A4LC 30 40 50 C CR...
Page 17: ...16 INDOOR UNIT COOLING ONLY MODEL ACK 30A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 18: ...17 INDOOR UNIT COOLING ONLY MODEL ACK 40 50A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50C...
Page 19: ...18 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 20: ...19 INDOOR UNIT HEAT PUMP MODEL ACK 30AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 21: ...20 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 23: ...22 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 24: ...23 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 26: ...25 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 27: ...26 INDOOR UNIT HEAT PUMP MODEL ACK 30AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 28: ...27 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 29: ...28 INDOOR UNIT COOLING ONLY MODEL ACK 15B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC15B...
Page 30: ...29 INDOOR UNIT COOLING ONLY MODEL ACK 20 25B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC20 25B...
Page 31: ...30 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC30C...
Page 32: ...31 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 33: ...32 INDOOR UNIT HEAT PUMP MODEL ACK 15BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 15BR...
Page 34: ...33 INDOOR UNIT HEAT PUMP MODEL ACK 20 25BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 20 25BR...
Page 35: ...34 INDOOR UNIT HEAT PUMP MODEL ACK 30BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30CR...