43
c)
Ensure that the compressor is not expose to open air for more than the recommended time specified
by its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the
compressor is about to be brazed.
d)
The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e)
When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
Composition of R407C in vapor
phase is different from liquid phase.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%
Dip-pipe
Invert cylinder
without dip-pipe
Liquid
withdrawal
Summary of Contents for A4LC 20B
Page 15: ...14 OUTDOOR UNIT ALC 30 40 50C CR A4LC 30 40 50 C CR...
Page 17: ...16 INDOOR UNIT COOLING ONLY MODEL ACK 30A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 18: ...17 INDOOR UNIT COOLING ONLY MODEL ACK 40 50A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50C...
Page 19: ...18 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 20: ...19 INDOOR UNIT HEAT PUMP MODEL ACK 30AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 21: ...20 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 23: ...22 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Page 24: ...23 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 26: ...25 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Page 27: ...26 INDOOR UNIT HEAT PUMP MODEL ACK 30AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Page 28: ...27 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Page 29: ...28 INDOOR UNIT COOLING ONLY MODEL ACK 15B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC15B...
Page 30: ...29 INDOOR UNIT COOLING ONLY MODEL ACK 20 25B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC20 25B...
Page 31: ...30 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC30C...
Page 32: ...31 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Page 33: ...32 INDOOR UNIT HEAT PUMP MODEL ACK 15BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 15BR...
Page 34: ...33 INDOOR UNIT HEAT PUMP MODEL ACK 20 25BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 20 25BR...
Page 35: ...34 INDOOR UNIT HEAT PUMP MODEL ACK 30BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30CR...