5
Operation
The parameterization and operation can be made by the integrated wired interface, dependent on the electronic variant.
Knowledge concerning the communication technology is provided.
5.1
Electronic output 09-A – 4…20mA, FSK interface
Configuration and data transmission can be made per standard FSK interface (e.g. isHRT USB resp. isHRT USBeX) and
operating software (e.g. PACTware). The use of the DTM isHRT CommDTM resp. ICS Generic HART DTM is recommended.
Information’s for installation resp. using the FSK interface resp. the operating software are not content of this manual.
Note:
Damping:
•
At a set damping 0s…<1s the communication is only active for 20s after power-up the supply voltage. After establishing
the connection it will be stay active. While this, the damping is set to 1s. After 4 minutes of inactivity the connection will
be terminated and the damping is reset to the set value.
•
At a set damping of ≥ 1s the establishing of a communication connection is always possible.
Default settings [Adjustment range]:
Default settings
Description
Address
0 [0…15]
Damping
1s [0s…60s]
Time till a change at the input has been processed
at the output by 100%.
Start value LRV
Nominal lower adjust value
LRV < URV
= 4mA
Span ≥ 25%
End value URV
Nominal upper adjust value
LRV < URV
= 20mA
Span ≥ 25%
5.2
Electronic output 09-V – Interface RS485 Modbus-RTU
Configuration and data transmission can be made per RS485 interface (e.g. Waveshare 15817) and operating software (e.g.
QModMaster). Information’s for installation resp. using the RS485 interface resp. the operating software are not content of
this manual.
Function code
Function
03
Read Holding Register
04
Read Input Register
06
Write Single Register
16
Write Multiple Register
Holding Register – Device settings
2 Byte – Uint16 - R/W
Address
Description
Default
Comment
2000
Modbus ID
1
Modbus ID / 1 … 247
2001
Baud-Rate
3
0 = 1200 / 1 = 2400 / 2 = 4800 / 3 = 9600
4 = 19200 / 5 = 38400 / 6 = 57600 / 7 = 115200
2002
Parity
2
0 = None / 1 = Odd / 2 = Even
2003
Number Stopbits
0
0 = 1 Stop Bit / 1 = 2 Stop Bit
2004
Word Order
0
0 = ABCD / 1 = CDAB
Input Register – Values
2 Byte – Read only
Address
Data Type
Description
1000
UInt16
Device Type
1001
UInt32
Serial Number
1003
UInt16
Calibration Date
1004
UInt16
Hardware Version
Input Register – Values
4 Byte – Float – Read only
Address
Data Type
Description
1010
Upper Range
PV = Pressure
1012
Lower Range
PV = Pressure
1014
Maximum
PV = Pressure
1016
Minimum
PV = Pressure
1018
Upper Range
SV = Temperature
1020
Lower Range
SV = Temperature
1022
Maximum
SV = Temperature
1024
Minimum
SV = Temperature
Input Register – Values
Read only
Address
Byte / Type
Description
Comment