4.2 

Electronic output 09-V – Interface RS485 Modbus-RTU

The Modbus protocol is a communication protocol, that base on a master/slave architecture. 

All devices are connected by two data wires (A+ / B-) and by one COMMON-wire (C/L-).

An original RS485 allows the connection of 32 slaves within one segment. The device has a load of only 1/8 of the standard 

load (Rin ≥ 96 k

Ω

), thus up to 256 of the devices can be theoretically operated within one network segment. However the 

number is limited to 247 due to the Modbus address space.
The both termination resistors RT prevent reflections on the data wires. The optimum resistor value depends on the wave 

impedance of the used cable, but a value of 120 Ohm is a popular choice.
The polarisation network is necessary, to ensure suitable potentials, if none of the devices transmits and thus the wires 

A+ and B- are undefined (high impedance). The value for RP depends e.g. on bus load or the termination resistors. 

Recommended values are between 450 Ohm and 650 Ohm.

The use of a polarisation network is recommended, to ensure a stable network. Usually the polarisation resistors are 

implemented within the master device or they are connectible.

Connect the device at bus topology (line). A stub line must be avoided.

Use a cable 4-core acc. to the EIA485 recommendations:

Impedance

135…165

 @ 3…20Mhz

Cable capacity

< 30pF/m

Cable diameter

> 0,64mm

Cable cross section

0,34 mm2 / AWG 22

Loop resistance   

< 110

/km

Shielding

Braided shield /shield foil

Cable length

38400 Baud ≤ 1200m

Observe maximum permitted supply voltage Us at the terminals L+/L-:

• 

Us = 6…35VDC

Summary of Contents for Hydrocont HP4SC

Page 1: ...OPERATING MANUAL BA03 22 Hydrocont HP4SC Hydrostatic filling level transmitter with capacitive ceramic measuring membrane...

Page 2: ...6 3 4 Field enclosure 7 4 Electrical connection 7 4 1 Electronic output 09 A 4 20mA FSK interface 7 4 2 Electronic output 09 V Interface RS485 Modbus RTU 8 5 Operation 9 5 1 Electronic output 09 A 4 2...

Page 3: ...ntal contamination can result Also the characteristics of the instrument can be impaired An inappropriately use disregarding the Operating manual and the technical rules using under qualified personne...

Page 4: ...08 0H 0 100 mwc 09 Electronic Output A Current 4 20mA FSK 2 wire over voltage protection 09 V RS485 Modbus RTU 4 wire over voltage protection 10 Electronic Function 0 without 10 1 Temperature Pt100 c...

Page 5: ...ead out at the version 09 V RS485 Modbus RTU by the digital interface or the resistance signal can be evaluated at the version 09 A current 4 20mA FSK in parallel to the pressure conditioned analogue...

Page 6: ...perature calmed places High process temperature steps can produce short time higher measuring signal deviations At underrun of the dew point e g cold process medium at high environmental temperature t...

Page 7: ...r to receive two or more digital actualizations per seconds from an intelligent field device The digital signal does not disturb the 4 20mA The communication protocol offers two simultaneous communica...

Page 8: ...the data wires The optimum resistor value depends on the wave impedance of the used cable but a value of 120 Ohm is a popular choice The polarisation network is necessary to ensure suitable potential...

Page 9: ...at the output by 100 Start value LRV Nominal lower adjust value LRV URV 4mA Span 25 End value URV Nominal upper adjust value LRV URV 20mA Span 25 5 2 Electronic output 09 V Interface RS485 Modbus RTU...

Page 10: ...nd device in for repair Supply voltage Operating voltage available Switch on resp repair operating voltage Check terminals resp repair Operating voltage too low too high Adapt operating voltage Load r...

Page 11: ...ility negligible Influence of auxiliary power 0 002 FSI V Influence of temperature Tk zero 0 015 FSI K 0 75 FSI Tk span 0 015 FSI K 0 5 FSI 0 4bar 4mwc 0 8 FSI 0 4bar 4mwc Influence of mounting positi...

Page 12: ...o PE 500VDC on request Rated leakage current 10kA 8 20 s Protection class III Pollution degree 4 Altitude 5000m above NN MTTF 463 4 years Weight 0 3kg L1 x 0 068kg m Materials Process wetted Ceramic A...

Page 13: ...rolsystem de 49 0 8721 9668 0 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 84307 Eggenfelden Germany 8 Dimensions 8 1 Sensor Electrical connection 14 K Confection stranded wires Electrical connection 14 H...

Page 14: ...rNi steel Art No 65001899 Dimensions in mm 9 2 Mounting screw VSM 1000 Thread ISO 228 1 G1 CrNi steel Gasket FKM FPM IP65 IP67 Art No 611000053 VSM 1500 Thread ISO 228 1 G1 CrNi steel Gasket FKM FPM I...

Page 15: ...rail width 22 5mm Art No 171000004 WTAU 100 U0 Pt100 isolation amplifier active 20 253Vuc In Pt100 Out 0 4 20mA 0 10V adjustable switch cabinet assembly at standard mounting rail width 22 5mm Art No 1...

Page 16: ...N E R F O R M E A S U R E M E N T A U TO M AT I O N ACS CONTROL SYSTEM GmbH Lauterbachstr 57 84307 Eggenfelden Germany info acs controlsystem de www acs controlsystem com 49 0 8721 9668 0 FEEL FREE T...

Reviews: