Model TT235-0600
RTD/Resistance Thermometer Transmitter w/USB
Acromag, Inc. Tel: 248-295-0880
- 26 -
http://www.acromag.com
[
26
]
https://www.acromag.com
Diagnostics Table
…
POSSIBLE CAUSE
POSSIBLE FIX
Cannot Calibrate Input Channel…
Is input wired properly?
Check that input is wired to ± input
terminals using correct polarity.
Cannot Measure Input Temperature or Resistance
…
Input may be wired incorrectly to
the input terminals.
Verify that the sensor or resistance decade
box is wired to the transmitter correctly.
Refer to Sensor Input Connections for wiring
sensors to the transmitter.
Service & Repair Assistance
This transmitter contains solid-state components and requires no maintenance,
except for periodic cleaning and transmitter calibration and verification (zero and
full-scale). Its enclosure is not meant to be opened for access and can be damaged
easily if snapped apart. It is highly recommended that a non-functioning transmitter
be returned to Acromag for repair or replacement. Acromag has automated test
equipment that thoroughly checks and calibrates the performance of each
transmitter, and can restore firmware. Please ref
er to Acromag’s Service Policy and
Warranty Bulletins, or contact Acromag for complete details on how to obtain
repair or replacement.