70
resistance
100-30000
696
09AC
External fault trip delay
R/W
0.1
~
600.0s
word
697
09AE
Start timeout trip
threshold
R/W
100%
~
200%
word
698
09AF
Start time
R/W
0.1
~
600.0s
699
09B0
Over power alarm
threshold
R/W
100
~
700%
700
09B1
Over power trip
threshold
R/W
100
~
700%
word
701
09B3
Over power trip delay
R/W
0.1
~
600.0s
702
09B6
Under power alarm
threshold
R/W
0
~
100%
703
09B7
Under power trip
threshold
R/W
0
~
100%
word
704
09B9
Under power trip delay
R/W
0.1
~
600.0s
705
09BF
Phase sequence trip
delay
R/W
0.1
~
600.0s
706
09C2
Short-circuit alarm
threshold when starting
R/W
400%
~
800%
707
09C3
Short-circuit trip
threshold when starting
R/W
400%
~
800%
word
708
09C4
Short-circuit alarm
threshold when running
R/W
400%
~
800%
709
09C5
Short-circuit trip
threshold when running
R/W
400%
~
800%
710
09C7
Short-circuit trip delay
R/W
0.1
~
600.0s
word
711
09CA
Fixed time limit
overload alarm
threshold
R/W
100-800%
word
712
09CB
Fixed time limit
overload trip threshold
R/W
100-800%
713
09CD
Fixed time limit
overload trip delay
R/W
0.1
~
600.0s
word
714
09D0
Voltage unbalance alarm
threshold
R/W
10
~
99%
715
09D1
Voltage unbalance trip
threshold
R/W
10
~
99%
716
09D3
Voltage unbalance trip
delay
R/W
0.1
~
600.0s
717
09D6
overflow protection
threshold
R/W
400%
~
800%
O
th
er
al
ar
m
718
09DF
Start times alarm
threshold
R/W
1-10 unti :time
719
09E0
Start times protection
delay
R/W
10-300min
720
09E1
Running time alarm
threshold
R/W
1000-60000 unit:hour
721
09E3
Fault times alarm
R/W
20-10000 unti:time