33
Alarm, trip
allowed
Alarm:allowed/forbid
den
Allow
Trip:allowed/forbidde
n
Allow
Current
imbalance
Tripping delay
0.1~600
1.0
S
Alarm
on/off
on
Tripping
on/off
on
Alarm threshold
10~80%
20
%
Alarm threshold
10~80%
30
%
Tripping delay
0.1~600
5.0
S
Action stage
Start:
allowed/forbidden
Forbidden
Run:
allowed/forbidden
Allow
Stop:
Allowed/forbidden
Forbidden
Alarm
on/off
On
Tripping
on/off
On
Locked rotor
Protection
Alarm delay
0.1-600.0s
0.1s
s
Tripping delay
0.1-600.0s
5.0s
s
AlarmThreshol
d
100-700%
500%
%
Trip Threshold
100-700%
600%
%
Action stage
Start:
allowed/forbidden
Allow
Run:
allowed/forbidden
Forbidden
Stop:
Allowed/forbidden
Forbidden
Return
coefficient
5%
Alarm, trip
allowed
Alarm:allowed/forbid
den
Allow
Trip:allowed/forbidde
n
Allow
Ground fault
protection
Alarm delay
0.1-600.0s
0.1s
s
Tripping delay
0.1-600.0s
0.1s
s
Alarm threshold
20-100%
20%
%
Trip Threshold
20-100%
50%
%
Action stage
and tripping
mode
Start:
allowed/forbidden
Allow
Run:
Allow