63
504
083C
Year,month
R/W
High byte:00-99,low
byte:0-12
word
505
083D
Day,hour
R/W
High byte:0-31, low
byte:0-23
word
506
083E
Minute,second
R/W
High byte:0-59, low
byte:0-59
word
507-549
083F
-0843
reserve
R
M
o
to
r
ru
n
n
in
g
in
fo
rm
at
io
n
550
08FC
Motor running time by
now
R
0-65535 h
word
551
08FD
Total motor stopping
times
R
0-65535 h
word
552
08FE
Total running times
R
0-65535 h
word
553
08FF
Total Stopping times
R
0-65535 h
word
554
0900
Total starting times
R
0-65535
word
555
0901
Total tripping times
R
0-65535
word
556
0902
DI STATE
R
Bit0-bit8 To Switch Input
DI1-DI9
word
557
0903
DO STATE
R/W
Bit0 relay 1, Bit1 relay 2,
Bit2 relay 3, Bit3 relay 4,
Bit4 relay 5, Bit5 relay 6
558
0904
DI/DO TYPE
R
0-DC type
;
1-AC type
559
0905
MOTOR STATE
R
bit0 readiness; bit1
Stopping; bit2 start; bit3
operation; bit4 alarm; bit5
tripping; bit7 0- Low speed
1- High speed
word
560
0906
Trip Breakdown fault
indication 1
R
Bit0 reverse time limit
overload tripping;
Bit1 grounding tripping;
Bit2 underload tripping
Bit3 disconnection;
Bit4 underpressure release;
Bit5 overpressure release;
Bit6 blocking and tripping;
Bit7 blocking tripping;
Bit8 current imbalance
tripping;
Bit9 PTC temperature
tripping;
Bit10 external failure
tripping;
Bit11 start timeout release;
Bit12 power tripping;
word